★★★★★
4.94 based on 219 reviews

🙶 First-time customer with Wake Industrial. The ordering process was completely seamless. The part that we o... 🙷

Request a Quote

Hero Image

Common Danfoss VFD Alarms – Codes, Causes, and Action

Wake Industrial is sharing information sourced from the original manufacturer's manual. Please be advised that Wake Industrial does not offer troubleshooting assistance through phone or email. For repair, replacement, or refurbishment needs, we invite you to use our quote form or call us at 1-919-443-0207. It is the user's responsibility to exercise independent judgment and caution when implementing these instructions. Wake Industrial shall not be held liable for any direct, indirect, incidental, or consequential damage to products or individuals resulting from the use of this information.

Contact Wake Industrial by calling 1-919-443-0207 or by filling out the quote form on this page to receive a comprehensive, industry competitive quote today. A Danfoss VFD alarm can stop production, interrupt pumping or leave an HVAC system offline. The displayed fault may originate in the incoming supply, motor, wiring, operating settings or drive electronics. Identifying the drive family and the conditions surrounding the trip helps narrow the checks before considering repair or replacement.

Before Resetting a Danfoss Drive

Record the complete message and whether the fault appeared at startup, during acceleration, under load or while stopping. Use the table for the correct family: VLT and VACON codes are not interchangeable, and some older VLT drives display fault names. Electrical checks require qualified personnel. Isolate all power sources, observe the specified discharge time and verify a safe condition before accessing connections. STOP/RESET does not provide electrical isolation.

VLT 2000 Alarm Messages

VLT 2000 drives distinguish between warning messages, trips and trip-locked conditions. Overvoltage during deceleration can result from the motor returning energy faster than the drive can dissipate it.

Alarm

Meaning

Likely cause

Corrective action

OVER VOLT

DC-link voltage too high

High supply voltage or short ramp-down time

Check the supply; review deceleration time and the installed braking arrangement.

UNDER VOLTAGE

DC-link voltage too low

Low supply voltage or missing mains phase

Check incoming voltage and phase availability.

OVER CURRENT

Excessive motor current

Excessive current demand or incorrect motor settings

Check motor parameters and whether the drive is correctly sized for the load.

GROUND FAULT / SHORT CIRCUIT

Ground fault or phase-to-phase short

Fault in the output circuit

Check installation and cabling. These conditions require power removal before reset.

VLT 2800 Protective Trips

The VLT 2800 monitors motor overload, power-module temperature and DC-link voltage. It also protects against output short circuits and earth faults; loss of a mains phase causes a shutdown.

Alarm

Meaning

Likely cause

Corrective action

Mains phase loss

An input phase is absent

Interrupted incoming phase

Check the supply circuit and connections.

Power-module overtemperature

Internal temperature exceeds the shutdown limit

Excessive thermal loading or inadequate cooling

Check installation and cooling conditions; allow the module to cool before reset.

DC-link overvoltage during braking

Regenerated energy raises bus voltage

Braking arrangement cannot absorb the returned energy

Check brake hardware and parameter 400, Brake function, against the installed configuration.

VLT 3000 Fault Messages

VLT 3000 fault messages distinguish drive overload from motor thermal protection. A motor trip can follow prolonged high current at low speed, while drive overtemperature directs attention to ventilation, cooling ribs and the fan.

Alarm

Meaning

Likely cause

Corrective action

OvervoltageExcessive DC-link voltageHigh mains voltage, transients or regenerationCheck the supply; review ramp-down time when the fault occurs during stopping.
OvercurrentInverter peak-current limit reachedPossible output short circuitCheck the motor and cable for ground faults.
Over-tempExcessive drive temperatureHigh ambient temperature, obstructed cooling ribs or defective fanImprove ventilation, clean cooling surfaces and replace a confirmed failed fan.
OverloadDrive thermal protection is activeMotor current exceeds the drive rating for too longReduce loading; reassess drive sizing if the required duty cannot be reduced.
Motor tripMotor thermal protection is activeExcessive current during prolonged low-speed operationReduce the low-speed load; assess motor sizing and additional cooling.
Click here to navigate to our VLT Drive guide.

VLT 5000 Signal and Motor Tuning Alarms

Loss of a reference signal, interrupted serial communication and failed motor adaptation require different checks from power-stage faults. The following code assignments apply specifically to VLT 5000 drives.

Alarm

Meaning

Likely cause

Corrective action

2 — Live zero

Terminal 60 current is below the configured detection threshold

Low or missing analog signal

Check the signal source, control wiring and minimum input scaling.

17 — Standard bus timeout

Serial communication with the drive has stopped

Communication interruption exceeding the configured interval

Check the controller, communication wiring and timeout settings.

22 — Motor adaptation failed

Automatic motor adaptation did not complete successfully

Incorrect motor data, motor-size mismatch, interrupted test or another reported fault

Read the detailed AMA message; verify motor data and sizing, and correct active alarms before repeating.

VLT Micro Drive FC 51 Braking Trips

On FC 51 drives, regenerated motor energy can raise the DC-link voltage during braking. Resistor braking requires both an integral dynamic brake and a connected external resistor.

Alarm/condition

Meaning

Likely cause

Corrective action

DC-link overvoltage during braking

Returned motor energy raises bus voltage above the permitted limit

Insufficient energy dissipation during generating operation

Check the installed braking arrangement, resistor connection where applicable, and brake-function selection.

VLT HVAC Drive FC 102 Brake Warnings and Trips

On FC 102 drives equipped with an integral dynamic brake, brake-power monitoring and brake-check settings determine the response to braking faults. The response can include a warning, a trip or a trip lock.

Alarm

Meaning

Likely cause

Corrective action

Brake-power warning/trip

Calculated resistor power exceeds the monitoring limit

Excessive braking duty or incorrect monitoring inputs

Check resistor value, braking duty and parameters 2-11, 2-12 and 2-13.

Brake-check failure

Brake-circuit monitoring detects a fault

Disconnected/shorted resistor or shorted brake IGBT

Have the resistor, connections and brake circuit checked before restoring operation.

VLT AQUA Drive FC 202 Alarms

FC 202 protection monitors electrical conditions as well as the load. A phase imbalance or missing supply phase can trigger a trip, while motor-generated energy can produce overvoltage during deceleration.

Alarm

Meaning

Likely cause

Corrective action

Alarm 16 — Short circuit

Output short-circuit protection operates; trip lock

Short circuit between motor phases

Have the output wiring and motor circuit checked before resetting.

Mains imbalance/phase loss

Supply imbalance produces excessive DC-bus ripple

Unbalanced supply or missing input phase

Check incoming phases and connections.

Motor-generated overvoltage

Regenerated energy raises DC-link voltage

Short deceleration time or a load driving the motor

Review stopping time, load behavior and the configured braking function.

VLT AutomationDrive FC 301 and FC 302 Alarms and Setup Checks

FC 301/302 drives monitor output short circuits, motor-phase loss and torque/current limits. A limit warning requires investigation of the load and settings; it does not by itself establish that the power stage has failed.

Alarm

Meaning

Likely cause

Corrective action

Alarm 16 — Short circuit

Inverter shuts down with trip lock

Short circuit between output phases

Check the motor circuit and output wiring before reset.

Missing motor phase

Motor-phase supervision detects a missing phase

Interrupted motor-phase connection

Inspect the motor circuit and review parameter 4-58.

Torque/current limit

Configured operating limit reached

Load demand exceeds the configured limit

Investigate loading and motor data before changing limits or trip delays.

Hardware or option incompatibility

Installed option must match the drive and slot

Incorrect option, slot or required operating system

Verify option compatibility and installation before substituting a card.

Initialization / defaults restored

Drive settings return to defaults

Initialization through parameter 14-22

Restore and verify the commissioned settings before restarting.

Click here to navigate to our Tech Spec breakdown on the 131H4347.

 

VACON NXL Fault Codes

VACON NXL stores faults in the H5 fault-history menu. Record that history when an intermittent fault cannot be reproduced immediately.

Fault 

Meaning

Likely cause

Corrective action

1

Overcurrent

Sudden load increase, motor-cable short or unsuitable motor

Check loading, motor size and cables.

2

Overvoltage

Short deceleration time or supply-voltage spikes

Review deceleration time and supply conditions.

3

Earth fault

Motor/cable insulation failure

Check motor cables and motor insulation.

14

Drive overtemperature

Restricted cooling or excessive thermal demand

Check airflow, heatsink cleanliness, ambient temperature and switching frequency.

VACON 20 HVAC Application Faults

The VACON 20 HVAC application records fault information in its history submenu. Capture available subcodes as well as the main fault number.

Fault

Meaning

Likely cause

Corrective action

9

Undervoltage

Low supply, power interruption or internal fault

Check supply voltage; request evaluation if the fault persists with a correct supply.

10

Input phase fault

Missing supply phase

Check supply voltage, fuses and cabling.

11

Output phase fault

No current in one motor phase

Check the motor cable and motor.

50

Analog input below range

Broken/loose control cable or failed signal source

Check the configured 4–20 mA or 2–10 V signal circuit.

WHY CHOOSE WAKE INDUSTRIAL?

Worldwide Shipping with FedEx, UPS, and DHL

1-Year Wake Industrial Warranty on All Products

We Are a Better Business Bureau A+ Business

Quick Response Within 15 Minutes During Business Hours

Expert Technicians Available Anytime

FAQs

Are Danfoss VLT and VACON fault codes interchangeable?

No. Use the drive family, application and complete displayed message to identify the fault.

Does an alarm always mean the drive needs repair?

No. Supply problems, motor faults, cabling and operating settings can also trigger protection.

Why does overvoltage appear when the motor stops?

The motor can return energy to the DC link during deceleration. Review stopping time and the braking arrangement.

Can resetting fix the underlying fault?

A reset clears the fault state when permitted; it does not correct damaged wiring, supply problems or excessive loading.

What does trip locked mean?

The fault requires the applicable power-removal and reset procedure after its cause is corrected. Discharge time varies by drive.

Should I increase current limits to stop trips?

First investigate loading, motor data and the configured protection. Raising a limit does not establish that operation is safe.

What should I send with a repair request?

Send the complete part/type number, nameplate photo, displayed fault, available history and a description of the operating conditions.

Motion Industries logo
3M logo
IBM logo
Gexpro Logo
Caterpillar logo
NASA logo
Ford logo
Vallen logo