The Beckhoff EK1100 is part of the EK EtherCAT Couplers series and supports up to 4.2 GB of addressable I/O points. It features two RJ45 bus connections and supports the Ethernet 100BASE-TX network standard with a maximum cable length of 100 meters. The coupler operates on a 24 VDC power supply and has an IP20 protection class.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The EK1100 is an EtherCAT bus coupler produced by Beckhoff within the EK EtherCAT Couplers series. It joins an EtherCAT fieldbus segment to the company’s E-bus I/O terminals so distributed signals can be gathered and forwarded to higher-level controllers. In automated cells, the unit acts as the physical and logical bridge that turns terminal-level data into deterministic Ethernet traffic, allowing modular machine sections to be linked without sacrificing cycle time.

The communication side uses a 100 MBaud transfer rate that matches the Ethernet 100BASE-TX standard and lets the device propagate telegrams through its two-port switch. Both network ports are presented as 2 x RJ45 sockets, simplifying daisy-chain wiring. Cabling distances can extend to 100 m between nodes, giving designers freedom in cabinet and machine layout. Telegram processing inside the coupler introduces only 1 µs of typical internal delay, so axis-level synchronization is maintained even in large lines. The coupler identifies itself on the network with the EtherCAT Device Protocol, and automatic addressing recognizes up to 4.2 GB of addressable I/O space without additional configuration steps. Hot-plugging of terminal strings is not available, so segments must be powered down when reconfigured. Electrical operating power for the electronics is supplied at 24 VDC, matching the control voltage found in most panels.

The supply rail is passed forward on power contacts rated for 24 VDC, 10 A, enabling sensors and actuators on the terminals to draw load current directly through the coupler. Downstream modules also receive logic energy through the E-bus, with a maximum backplane output of 5 V, 2 A that supports sizeable terminal stacks before an auxiliary feeder is required. Internal electronics draw 70 mA + (Σ E-bus current / 4), a figure useful when planning cabinet power budgets. The enclosure is classified as IP20, so installation must be inside a shielded cabinet to avoid dust or finger contact.

Addressable Io Points
4.2 GB
Bus Connection
2 x RJ45
Current Consumption
70 mA + (Sum E-bus current/4)
Data Rate
100 MBaud
Delay
1 µs typ.
Hotconnect
No
Max Cable Length
100 m
Max E-bus Output
5 V, 2 A
Network Standard
Ethernet 100BASE-TX
Power contacts
24 VDC, 10 A
Power Supply
24 VDC
Protection Class
IP20
Protocol
EtherCAT Device Protocol
LED / Error indication Likely cause Recommended corrective action
Us LED (green) OFF – no bus-coupler supply 24 V DC absent or < 20 V at the EK1100 feed terminals Verify upstream PSU is on, measure 24 V across pins 1-3, check fuses & wiring; restore nominal 24 V DC.
Up LED (green) OFF – no power-contact supply 24 V field-power feed to I/O power contacts missing or fuse tripped Feed 24 V to power-contact pins — typical fix is to add/replace EL9410 feed terminal or reset field-power fuse.
RUN LED flashing (Pre-OP) EtherCAT master has not driven the slave into OP state (configuration or mapping mismatch) Compare actual terminal order with TwinCAT project; reload scan, check PDO mapping, then “Activate Configuration” to reach OP.
RUN LED OFF (INIT) Master not communicating (cable unplugged, master stopped, or wrong Net ID) Ping AMS Net ID, inspect cables; power-cycle slave after restoring link to re-enter Pre-OP/OP.
ERR LED continuous flash General K-bus fault (often EMC, severe undervoltage/overvoltage) Check supply stability, add surge suppression, then power-cycle; if flash persists, isolate terminals one-by-one.
ERR LED 1 pulse / pause / 1 pulse EEPROM checksum error in Bus Coupler Load factory settings via TwinCAT → “Coupler → Services → Factory Setting”, then restart.
ERR LED 2 pulses Programmed configuration entry invalid or missing module Rescan terminals in TwinCAT, correct I/O list, download configuration.
ERR LED 4 pulses K-bus data error / break behind EK1100 Check that first I/O terminal is firmly seated; replace damaged terminal or add EL9011 end cap.
LINK/ACT LED (X1 IN) OFF No physical link from EtherCAT master Inspect/replace CAT-5e/6 cable, confirm switch port, verify ≤100 m run.
LINK/ACT LED (X2 OUT) OFF Downstream cable/device missing or faulted – network stops at EK1100 Check daisy-chain cable to next slave; if unused, fit protective RJ45 plug or end the line here.
Model Primary role Interface / ports Max link distance
EK1100 Baseline EtherCAT copper coupler for EL/ES terminals 2 × RJ45 (100BASE-TX) 100 m
EK1101 Copper coupler with ID switch & Fast Hot Connect 2 × RJ45 (100BASE-TX) 100 m
EK1110 EtherCAT extension (line repeater) 1 × RJ45 out + internal E-bus 100 m
EK1122 2-port EtherCAT junction (star/branch) 2 × RJ45 (100BASE-TX) 100 m per branch
EK1501 Multimode fiber-optic coupler (media converter) 2 × SC-duplex (100BASE-FX) 2 km
EK1521 1-port fiber-optic junction 1 × SC-duplex (100BASE-FX) 2 km (multi-mode) / 20 km†
AL status code What it means
0x0001 Unspecified error
0x0002 No memory (out-of-RAM in ESC)
0x0011 Invalid requested state change
0x0012 Unknown requested state
0x0017 Invalid Sync-Manager configuration
0x0019 No valid outputs available
0x001B Sync-Manager watchdog elapsed
0x001F Invalid watchdog configuration
0x0024 Invalid input mapping
0x0034 DC Sync timeout

Frequently Asked Questions about EK1100:

Q: What power supply voltage is required for the EK1100 EtherCAT Coupler?

A: The EK1100 uses a 24 VDC power supply for its operation.

Q: What is the maximum E-bus output provided by the Beckhoff EK1100?

A: This model supports a maximum E-bus output of 5 V at 2 A for connected terminals.

Q: What type of bus connection does the EK1100 feature?

A: The EK1100 EtherCAT Coupler communicates via 2 x RJ45 bus connections.

Q: How many addressable I/O points are supported on the EK1100 coupler?

A: The EK1100 can support up to 4.2 GB of addressable I/O points.

Q: What network standard and data rate does the EK1100 EtherCAT Coupler use?

A: The network standard for the EK1100 is Ethernet 100BASE-TX, ensuring a data rate of 100 MBaud.


Internal Product Review

  • ‘‘The EK1100 is a Beckhoff EtherCAT coupler with 2 x RJ45 bus connections and Ethernet 100BASE-TX support. Fast 100 MBaud communication and a typical 1 µs delay give the unit very responsive network performance in distributed I/O architectures. IP20 protection and a 24 VDC power supply make the coupler a dependable choice for control cabinet integration.’’