EK1914 Beckhoff

In-Stock, Ships 3-5 Days

Preparing your secure checkout page...

The Beckhoff EK1914 is part of the EK EtherCAT Couplers series and supports the EtherCAT Device Protocol at a baud rate of 100 MBaud. The unit provides 4 standard inputs and outputs as well as 2 safe inputs and outputs, with a supply voltage of 24 VDC. It features IP20 protection class and comes with two RJ45 bus connections.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The EK1914 is an EtherCAT coupler manufactured by Beckhoff as part of the EK EtherCAT Couplers series. Serving as the first node in a terminal string, it converts high-speed fieldbus telegrams into local I/O updates so that digital signals from sensors and actuators can be exchanged deterministically with the PLC. By combining standard and safety channels in one device, the coupler streamlines wiring and shortens response paths in industrial automation cells that demand synchronized motion, interlocked guarding, and compact control cabinets.

Two network sockets arranged in a daisy chain use 2 x RJ45 connections, providing the real-time link and line continuation for additional nodes. The electronics and field circuits share a protective extra-low-voltage supply of 24 V DC, keeping signal levels consistent with PELV requirements. Physical space inside a control cabinet is minimized by the housing size of 44 mm × 100 mm × 68 mm, allowing dense mounting next to standard Bus Terminals. A built-in digital filter of 500 µs suppresses contact bounce on the four standard input channels so the controller receives debounced states without extra software delays. Typical system latency from a safe input change to the corresponding safe output actuation is 4 ms, which supports rapid stop functions when integrated with drives or contactors.

The functional safety layer complies with PL e according to ISO 13849-1, and the module therefore provides two independent safe inputs and two safe semiconductor outputs for emergency-stop circuits. In the event of internal faults, the probability of a dangerous failure per hour is limited to 2.64 × 10⁻⁹, meeting Category 4 architectures when used with certified wiring. Each safe output can source up to 500 mA, while standard channels are limited to 0.5 A, enabling direct switching of contactors and indicator loads without relays. Environmental ingress is restricted by the IP20 enclosure, so the coupler must be housed inside a cabinet with controlled ambient conditions.

Bus Connection
2 x RJ45
Dimensions (w X H X D)
44 mm x 100 mm x 68 mm
Input Filter
500 µs
Max Safe Output Current
500 mA
Max Std Output Current
0.5 A
Performance Level
e
Pfhd
2,64E-09
Protection Class
IP20
Protocol / Baud Rate
EtherCAT Device Protocol / 100 MBaud
Reaction Time (typ.)
4 ms
Safe Inputs
2
Safe Outputs
2
Standard Inputs
4
Standard Outputs
4
Supply Voltage (pelv)
24 VDC
Symptom / LED pattern Likely root cause First corrective action
DC LED dark – all LEDs off 24 V DC absent or < 22 V Measure supply at power contacts; replace blown fuse or tighten spring-clamp plug 
RUN LED off, ERR LED red immediately after power-up Hardware self-test failed Power-cycle ≥ 10 s; if state returns, replace coupler
RUN LED 2 Hz green (stuck in PRE-OP) Master never downloaded configuration In TwinCAT/TIA download & activate the EL-terminal map, then restart scan 
RUN LED 1 Hz green (SAFE-OP) PDO length/order mismatch Check terminal order vs. PLC config, correct, and restart EtherCAT 
Diag 2 LED steady red External supply or cross-circuit detected on safe channels Remove stray 24 V, check wiring, then reboot – LED must go out 
Diag 2 LED blink-code 2-1-1-1 / 3-1-1-1 Over-temperature on µC1 / µC2 Keep cabinet ≤ 55 °C, clear airflow, leave ≥ 30 mm headroom 
Diag 1 LED stays dark FSoE (TwinSAFE) communication not running Check TwinSAFE address & wiring; leave Reset state to start FSoE 
CF LED red CompactFlash® card missing or CRC error Reseat card; if red after reboot, clone & replace CF card 
LINK/ACT LEDs dark, master logs “Lost slave” Broken RJ-45 or switch port down Swap cable, clean contacts, verify 100 Mb link & shielding (bresimar.pt)
ERR LED triple-flash (Hot-Connect fault) Duplicate rotary ID in the segment Give every EK1914/EK1101-family coupler a unique ID switch setting 
Model Integrated I/O (standard / safe) Special feature(s) Hot Connect Typical spot to use it
EK1914 4 DI + 4 DO / 2 FS-DI + 2 FS-DO Compact TwinSAFE coupler with FSoE Yes Small cells needing a handful of safe & standard signals 
EK1814 4 DI + 4 DO / — Low-cost standard I/O coupler No Simple machines with limited I/O 
EK1818 8 DI + 4 DO / — “Preferred type” – more inputs No Sensor-heavy conveyors or packaging lines 
EK1828 4 DI + 8 DO / — Output-heavy variant No Valve blocks, indicator lamps, solenoids 
EK1101-0080 none / — Fast-Hot-Connect coupler with ID switch Yes (FHC) Robot end-effectors that dock/undock frequently 
EK1300 none / — EtherCAT-P coupler (power + data in one M8 cable) Yes Single-cable sensor/actuator islands, retrofit panels 
LED / code Meaning
DC LED dark 24 V absent / < 22 V
RUN LED off + ERR red at power-up HW self-test fail (INIT)
RUN 2 Hz green (PRE-OP forever) PLC never sent configuration
RUN 1 Hz green (SAFE-OP) PDO size/order mismatch
ERR 1-flash red EEPROM / firmware CRC error
ERR 3-flash red Duplicate Hot-Connect ID
Diag 2 LED steady red External 24 V on safe channel / cross-circuit
Diag 2 blink 2-1-1-1 µC 1 over-temperature
Diag 2 blink 3-1-1-1 µC 2 over-temperature
CF LED red CompactFlash missing / CRC error

Frequently Asked Questions about EK1914:

Q: What type of bus connection does the EK1914 EtherCAT coupler use?

A: The EK1914 connects to fieldbus systems using 2 RJ45 ports supporting EtherCAT device protocol at 100 MBaud.

Q: What supply voltage is required for the EK1914?

A: This coupler operates on a 24 VDC supply voltage (PELV), suitable for industrial automation environments.

Q: How many safe inputs and outputs are available on the EK1914?

A: The EK1914 provides 2 safe inputs and 2 safe outputs for use in safety-relevant control systems.

Q: What are the standard and safe output current limits for the EK1914?

A: The EK1914 supports a maximum standard output current of 0.5 A and a maximum safe output current of 500 mA.

Q: What is the input filter specification for the EK1914?

A: This model features an input filter with a response time of 500 μs for input signal conditioning.


Internal Product Review

  • ‘‘The EK1914 is a Beckhoff EtherCAT coupler built for safety-oriented I/O integration, with 2 safe inputs and 2 safe outputs. EtherCAT device protocol at 100 MBaud and dual RJ45 bus connections support clean network integration and stable field communication. Performance Level e makes the coupler an excellent choice for high-integrity control architectures.’’