The X20BC00E3 is a fieldbus I/O module by B & R Automation and is part of the X20 Fieldbus Input Output Modules series. It supports the PROFINET IO protocol, features an integrated 2-port switch, and provides 2 RJ45 ports. The unit has a depth of 75 mm, width of 37.5 mm, and height of 99 mm.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

B&R Automation's X20BC00E3 module belongs to the X20 Fieldbus Input Output Modules series and acts as a gateway between distributed I/O slices and controller networks. Within an X20 rack, it collects sensor states and forwards actuator commands so higher-level PLCs can coordinate machine functions over standard Ethernet. The unit mounts on a DIN rail next to power supplies and slice controllers, providing deterministic exchange cycles typical of real-time Ethernet systems. This layout supports modular expansion in packaging lines, conveyors, and assembly cells where local I/O must remain closely coupled to the control network.

The housing is 75 mm deep, 37.5 mm wide, and 99 mm high, allowing the device to fit inside shallow cabinets while leaving space for front cabling. Communication is handled through PROFINET IO, letting controllers perform cyclic data exchange with real-time Ethernet timing. Two shielded network paths are present, and both are accessible through 2 integrated RJ45 connectors, so adjacent devices can remain linked in a compact line topology. Because only one fieldbus interface is integrated, the communication path remains focused on a single network role rather than dividing resources across multiple protocols.

Power and backplane identification are established through a 24 VDC keying voltage that prevents insertion of incompatible bases. Network distribution is aided by the module's integrated 2-port switch, so line topologies remain intact even when the unit is removed under power. I/O slices connect through 12 coded terminal pins that carry supply and signal buses, while the defined 1 fieldbus channel keeps network exchange direct and organized. This arrangement helps the rack maintain a clear separation between network traffic, slice interconnection, and local power distribution.

Depth
75 mm
Fieldbus Count
1
Fieldbus Protocol
PROFINET IO
Height
99 mm
Keying Voltage
24 VDC
Rj45 Ports
2
Switch Type
Integrated 2-port switch
Terminal Pins
12
Width
37.5 mm

Frequently Asked Questions about X20BC00E3:

Q: What fieldbus protocol is supported by the X20BC00E3 module?

A: The X20BC00E3 module uses PROFINET IO as its fieldbus protocol.

Q: What type of network switch does the X20BC00E3 have?

A: This module features an integrated 2-port switch for network connectivity.

Q: How many RJ45 ports are available on the X20BC00E3?

A: It is equipped with two RJ45 ports to facilitate Ethernet connections.

Q: What is the keying voltage needed for the X20BC00E3 module?

A: The X20BC00E3 module requires a keying voltage of 24 VDC for operation.

Q: Which series does the X20BC00E3 module belong to?

A: This module is part of the X20 Fieldbus Input Output Modules series from B & R Automation.

Front-LED / symptom Likely cause First corrective action
DC LED off – no LEDs lit 24 V supply absent or < 22 V Measure voltage at the X20 terminal block; replace/retighten cabinet fuse and PE ground
Module-status LED quad-flash (red) Controller has no valid IP address (0.0.0.0) Verify IP / DHCP settings in the PLC or assign a fixed device address
Module-status LED double-flash (red) Unacknowledged diagnostic alarm Open the PROFINET master diagnostic list, clear alarm and reset the slave
Module-status LED “Blink 1” (green) Boot phase – I/O modules are being initialised Wait until initialisation finishes; if it loops, check X2X-bus wiring
Module-status LED “Blink 3” (green) Configuration of I/O modules in progress Confirm GSDML settings match the physical node order
Module-status LED “Blink 4” (green) Bus-controller has detected a configurable error Correct the fault in the PLC engineering tool while online
RUN LED off although master is RUN PROFINET master not yet started or wrong device name Check PLC is in RUN and the station-name exactly matches the configured one
CF LED red steady / flashing CompactFlash missing, corrupt or write error Reseat CF card, clone from backup image or replace card if errors persist
LINK/ACT LEDs dark, BF on master Cable fault or switch port down Replace Ethernet patch lead, verify 100 Mb full-duplex and shield continuity
Rising cabinet temperature > 60 °C → resets CPU thermal derate Improve ventilation, keep ambient ≤ 55 °C, leave ≥ 30 mm free space above module
Model Field-bus interface Integrated switch / hub Min. field-bus cycle Typical I/O size (In/Out)
X20BC00E3 PROFINET IO Conformance Class B 2-port 100 Mb switch (RJ45) 1 ms 1440 B / 1440 B
X20BC00G3 EtherCAT slave 2-port 100 Mb switch (RJ45) 200 µs typ. 1024 B / 1024 B
X20BC0083 POWERLINK CN 2-port hub (RJ45) 200 µs 1486 B / 1486 B
X20BC0087 Modbus TCP / UDP 2-port 100 Mb switch (RJ45) 1 ms typ. 1024 B / 1024 B
X20BC0088 EtherNet/IP adapter 2-port DLR-ready (RJ45) 1 ms RPI min. 511 B / 511 B 
X20BC1484 CANopen + POWERLINK 2-port hub + CAN (DB9) 1 ms (PL) 512 B / 512 B
LED blink / status* Meaning
DC OFF (all LEDs dark) 24 V missing or < 22 V
Module-LED quad-flash πŸ”΄πŸ”΄πŸ”΄πŸ”΄ No valid IP address (0.0.0.0)
Module-LED double-flash πŸ”΄ πŸ”΄ Pending diagnostic alarm from I/O slice
Module-LED “Blink 1” 🟒 Boot phase – X2X modules initialising
Module-LED “Blink 4” 🟒 Configuration error in I/O map
RUN LED OFF while PLC RUN Wrong PROFINET device-name
CF LED red CompactFlash missing / CRC error
LINK/ACT LEDs dark – BF on PLC Ethernet cable or switch port down
R LED red steady Hardware fault / self-test fail
Over-temp log entry Heatsink > 70 °C – auto reset

Internal Product Review

  • β€˜β€˜The X20BC00E3 is a B & R Automation fieldbus I/O module designed for PROFINET IO networks with an integrated 2-port switch. The 24 VDC keying voltage and dual RJ45 ports make commissioning straightforward and support clean network integration, making this module a strong fit for distributed automation.’’