DCD50 Kollmorgen
Wake Industrial LLC is not an authorized distributor of this product.
MPN: 83A21050A-0002
The DCD50 cooling unit from Kollmorgen belongs to the AC SuperDrive Motion Units, offering a nominal cooling capacity of up to 50 kW. It features passive and active rear door cooling with chilled water inlet temperatures of 12 °C to 18 °C. Weighing 230 lbs, it supports rack enclosures up to 42U high.
Internal Product Review
The DCD50 is a high-quality cooling unit for industrial applications. With a wide operating temperature range, the unit uses chilled water as the coolant. Its high-performance makes it suitable for long-term use.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The DCD50 cooling unit from Kollmorgen is noted for its high versatility. This product is used with the manufacturer’s AC superdrives. The device is intended to be operated only for industrial use. The unit features passive and active rear door cooling mechanisms. It uses chilled water as its coolant. This cooling system can be mounted onto a rack enclosure that has a height of 42 units.
The product has a dedicated inlet and outlet for the coolant. This device supports a nominal cooling capacity of up to 50 kW. The unit features a maximum installation altitude of 2700 m above sea level. It must be handled carefully to avoid the chances of it getting damaged. This cooling unit must be stored only after its coolant has been removed. The product is meant to be operated at a temperature ranging from 10 °C to 40 °C. This device depicts a maximum operating pressure of 10 bar or 145 psi. The unit has an active air flow rate of 9000 m³/h with N+1 fan redundancy and 10800 m³/h without any redundancy. It portrays reduced performance when the ambient operating conditions are exceeded.
This cooling unit has a size of 77 x 23 x 9-3/8 (H x W x D) inches and a weight of 230 lbs without the coolant. The product portrays a maximum power consumption of 1185 W. This device is intended to be stored at a temperature between -25 °C and 80 °C. The unit has a temperature range of 12 °C to 18 °C for its inlet while the minimum and maximum temperatures for the outlet are 18 °C and 24 °C respectively. It must be handled and operated only by people with the expertise to do so.