4.95 based on 202 reviews

🙶 Wake was very helpful in getting us a servo motor and drive for our tube mill line. This was the first tim... 🙷

09.E5.T60-1001 KEB

In-Stock, Ships 3-5 Days
Current Response Time 6 min 30 sec
No Hidden Fees Rush or Credit Card
No Tariffs On US Orders

Internal Product Review

The 09.E5.T60-1001 is a KEB Combiline EMC filter designed for 3 Ph + PE systems in the 400/480 V AC class. C1 EMC performance across 0.15-30 MHz gives the filter strong noise attenuation in sensitive panel applications. A 5.3 A rating with support for 30 m motor cable length makes this filter a strong choice for dependable inverter installations.

Sell Part
Have a part to sell?
Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The 09.E5.T60-1001 is an electromagnetic compatibility line filter built by KEB for the Combiline EMC Filters series. It is intended for placement between the mains supply and an AC drive so that conductive emissions from switching devices stay below statutory limits in industrial automation cells. Filtering of differential-mode and common-mode noise helps protect neighboring control hardware and keeps motor cables from acting as unintended antennas. This also helps reduce high-frequency interference returning to the supply network from the drive.

It handles a three-phase plus protective-earth supply and tolerates up to 528 V AC, aligning with the series rating for 400/480 V AC grids. A continuous load current of 5.3 A can flow without saturating the magnetic core. The attenuation band spans 0.15–30 MHz, targeting the primary spectrum generated by pulse-width-modulated drives. Grid compatibility is maintained over 50/60 Hz operation with a ±10% margin, and earth-referenced leakage stays within 15 mA so residual-current devices can still be used. Internal dissipation is limited to 15 W, and EMC classification C1 allows installation in sensitive environments. Connections are made through 1.5 mm² screw terminals, and the input uses a three-phase plus protective-earth configuration.

The enclosure is 191 mm high, 75 mm wide, and 40 mm deep, yet it weighs only 1 kg, which helps with DIN-rail or back-plate mounting. Continuous service is permitted up to 45 °C ambient, and within this range the 15 W of power loss is dissipated by natural convection through the steel housing. A permissible motor-cable distance of 30 m allows the motor to be mounted away from the control cabinet without exceeding conducted-emission limits. The slim housing also leaves room for adjacent components in compact enclosures.

Depth
40 mm
Emc Class
C1
Frequency Range
0.15-30 MHz
Height
191 mm
Input Phases
3 Ph + PE
Leakage Current
15 mA
Line Frequency
50/60 Hz ±10%
Max Ambient Temp
45 °C
Max Input Voltage
528 V AC
Motor Cable Length
30 m
Power Loss
15 W
Rated Current
5.3 A
Terminal Size
1.5 mm²
Voltage Class
400/480 V AC
Weight
1 kg
Width
75 mm

Frequently Asked Questions about 09.E5.T60-1001:

Q: What is the maximum input voltage supported by the 09.E5.T60-1001 EMC filter?

A: The 09.E5.T60-1001 is rated for a maximum input voltage of 528 V AC.

Q: What is the rated current capacity of the 09.E5.T60-1001 model?

A: This EMC filter can handle a rated current of 5.3 A.

Q: Which EMC class does the 09.E5.T60-1001 filter belong to?

A: The 09.E5.T60-1001 is classified as an EMC Class C1 device.

Q: What frequency range does the 09.E5.T60-1001 EMC filter cover?

A: The allowable frequency range for this model is from 0.15 to 30 MHz.

Q: What is the maximum motor cable length supported by the 09.E5.T60-1001 filter?

A: The 09.E5.T60-1001 supports a motor cable length of up to 30 meters.

Motion Industries logo
3M logo
IBM logo
Gexpro Logo
Caterpillar logo
NASA logo
Ford logo
Vallen logo