The 131L9901 is a panel-mounted drive with IP20 protection and a motor power of 55.0 kW. Manufactured by Danfoss as part of the VLT FC 101 HVAC Basic Drives, it features a frame size of H7 and an input voltage range of 380-480 V 3-phase. This unit measures 807 mm in height, 329 mm in width, and weighs 43 kg.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
131L9901 is a Danfoss VLT FC 101 AC drive. It is manufactured for use in HVAC applications. The main benefit of using the drive to control pumps and fans is significant energy savings. Compared to other methods, use of a drive for pressure/flow control also provides better control. Shaft output of the 131L9901 drive is 55 kilowatts (70 Horsepower). Size of the IP20 enclosure is H7. The maximum specified cable size is 1 AWG. At 40 ⁰C, the continuous output is 106 Amps when the input voltage is between 380 and 440 Volts and can go up to 116 Amps for 60 seconds. At 40 ⁰C, the continuous output is 105 Amps when the input voltage is between 441 and 480 Volts and can go up to 115 Amps for 60 seconds.
At 50 ⁰C, the continuous output is 74.2 Amps when the input voltage is between 380 and 440 Volts and can go up to 81.6 Amps for 60 seconds. At 50 ⁰C, the continuous output is 73.5 Amps when the input voltage is between 441 and 480 Volts and can go up to 80.9 Amps for 60 seconds. The continuous and intermitted input at 380 to 440 Volts is 103 Amps and 113 Amps. The continuous and intermitted input at 441 to 480 Volts is 88.6 Amps and 97.5 Amps. During operation, typical power loss for the 131L9901 drive is 1133 Watts. Weight of the unit is approximately 36 kilograms and the efficiency - as tested - is 98.2%. With four slot for optional modules, the drive offers flexibility, and operators can install modules in the field to add needed features at any time.
Frequently Asked Questions about 131L9901:
Q: Is a brake chopper installed on the unit?
A: A brake chopper is not installed on the unit.
Q: Is a control panel available on the drive?
A: A control panel is not available on the drive.
Q: Are any option modules installed on the drive?
A: Options modules are not installed on the drive.
Q: Is an RFI filter installed on the drive?
A: The drive includes an internal RFI filter.
Q: Are I/Os available on the drive?
A: Available I/Os include 2 analog outputs, 2 digital outputs, and 2 relay outputs.