FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
-
In-Stock, Ships 3-5 Days
The FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0 is equipped with a vector control type without an encoder. Manufactured by Danfoss, part of the VLT AutomationDrive FC 302 Series, it operates with a three-phase voltage of 380-500 V. The drive includes an integrated EMC filter and 160% overload capacity for 60 seconds.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0 is one of VLT Automation’s most remarkable frequency converters. With an advanced 302 drive, this frequency converter from Danfoss operates at a wide voltage and temperature range. Particularly, the FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0 can operate seamlessly at a supply range of 380 to 500 V, plus or minus 10%. From its official datasheet, the FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0 exhibits an estimated power loss of 62 watts and an efficiency of 97% during full-load operation. At this operating point, the frequency converter reaches a typical shaft output of 1.5 kW. For FC-302 variable drives by Danfoss, the default IP 20 chassis is the A2 enclosure. This enclosure protects the device from particulates with a diameter of 12.5 mm or larger.
At high-overload conditions, the FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0 delivers a maximum input current of 5.9 A for sixty seconds. For continuous operation modes, the maximum input current for this converter is 3.7 A. At the maximum continuous input current, the corresponding output current of the converter is 4.1 A. To safely draw the rated currents at full-scale operating modes, the mains and motor cables must have a maximum cross-section of triple 12 AWG. Like all other Danfoss’ variable frequency drives, the FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0 has an energy efficiency class of IE2 and a max THD of 10%.
The FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0 has a true power factor of 0.9 at its rated load. For a temporary period of time, the converter can withstand a maximum phase voltage imbalance of 3% of the rated phase voltage. The converter can operate safely at a supply frequency of 50 or 60 hertz, with a maximum deviation tolerance of 5%. At flux mode, the motor output of the frequency converter has a maximum torque rise time of 1 millisecond.
Frequently Asked Questions about FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0:
Q: What is the maximum load output for the FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0’s 10 V DC output control card?
A: The FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0’s 10 V DC output control card can have a maximum load output of 15 mA.
Q: What is the maximum load output for the FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0’s 24 VDC output control card?
A: The FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0’s 24 VDC control card can have a maximum load of 200 mA.
Q: What terminals correspond to the FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0’s 24 VDC output control card/s?
A: Terminals 12 and 13 correspond to the control card 24 VDC output of the FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0.
Q: How many digital outputs can the FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0 support?
A: The FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0 can support up to two digital outputs during operation.
Q: What terminals can be used for the pulse and encoder inputs of the FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0?
A: Pulse inputs for the FC-302P1K5T5E20H1BXXXXXSXXXXA0BXCXXXXD0 can be connected to terminals 29 and 33, whereas encoder inputs can be connected to terminals 32 and 33.