Internal Product Review

The FC-302N132T5134G9606H2BGXXXXSXXXXAXBXCXXXXDX is a Danfoss VLT FC 302 automation drive rated at 132 kW for 380-500 VAC systems. Included brake chopper support and 160% starting torque for 60 s give this unit strong control authority during demanding acceleration and braking cycles. High-speed capability up to 590 Hz and a displacement power factor above 0.98 make this drive an excellent choice for efficient, high-performance automation.

Sell Part
Have a part to sell?
Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The FC-302N132T5134G9606H2BGXXXXSXXXXAXBXCXXXXDX drive is produced by Danfoss for the VLT FC 302 Automation Drives series. It is a cabinet-mounted AC variable frequency converter that modulates motor voltage and frequency so plant controllers can match motor speed to process demand. Its closed-loop vector algorithms maintain accurate torque at very low rotor speeds. Integrated logic supervises torque, ramp times, and braking energy, allowing the drive to replace mechanical throttling devices and reduce energy use in industrial pumping, ventilation, and material-handling systems.

With a 400 V-class supply, the inverter delivers a rated output of 132 kW while drawing up to 251 A from a mains input range of 380 to 500 VAC. The power section can generate carrier-based output frequencies up to 590 Hz, while its flux-control path supports frequencies up to 300 Hz. These limits establish the usable speed range for high-pole or dynamically derated motors. During startup, the current-regulated algorithm supplies 160% of nominal torque for 60 s. An internal brake chopper safely dissipates regenerative energy during deceleration.

Torque commands have a flux rise time of 1 ms, allowing rapid correction after load changes. For variable-torque loads, the drive can provide 110% output for 0.5 s without causing a thermal trip. Continuous full-load operation is permitted at an ambient temperature of 45 °C, and the unit can operate at temperatures up to 55 °C with proportional derating. The displacement power factor exceeds 0.98, while the true power factor remains at or above 0.9 to minimize upstream transformer loading. Shielded motor cables may extend up to 150 m, while unshielded cable runs may extend up to 300 m. A front-mounted LCP 102 keypad provides local access to operating parameters and supports multiple languages.

Brake Chopper
Included
C1 Option
No C1 Option
Displacement Power Factor
>0.98
Full-load Ambient
45 °C
Input Current (380–440 V)
251 A
Language Pack
Standard
Local Control Panel
LCP 102
Mains Voltage
380 - 500 VAC
Max Ambient With Derating
55 °C
Max Flux Frequency
300 Hz
Max Output Frequency
590 Hz
Power Phase
Three Phase Power
Product Group
VLT AutomationDrive FC
Rated Power
132 kW
Series Identifier
302
Shielded Motor Cable
150 m
Starting Torque
160% for 60 s
Torque Rise Time (flux)
1 ms
Torque Rise Time (vvc+)
10 ms
True Power Factor
≥0.9
Unshielded Motor Cable
300 m
Variable-torque Overload
110% for 0.5 s

Frequently Asked Questions about FC-302N132T5134G9606H2BGXXXXSXXXXAXBXCXXXXDX:

Q: Does the FC-302N132T5134G9606H2BGXXXXSXXXXAXBXCXXXXDX include a brake chopper?

A: A brake chopper is included in the configuration for this drive.

Q: What is the rated power of the Danfoss FC-302N132T5134G9606H2BGXXXXSXXXXAXBXCXXXXDX?

A: The rated power of this model is 132 kW, making it suitable for demanding industrial applications.

Q: What mains voltage range is supported by this FC-302N132T5134G9606H2BGXXXXSXXXXAXBXCXXXXDX drive?

A: This drive supports a mains voltage range from 380 to 500 VAC on three phase power.

Q: What starting torque can the FC-302N132T5134G9606H2BGXXXXSXXXXAXBXCXXXXDX deliver?

A: The starting torque is specified at 160% of rated torque for 60 seconds.

Q: What is the maximum output frequency of the FC-302N132T5134G9606H2BGXXXXSXXXXAXBXCXXXXDX?

A: Maximum output frequency for this drive is 590 Hz, allowing operation with high-speed motors.