132L4429

    In-Stock, Ships 1-2 Days

Preparing your secure checkout page...

The 132L4429 drive features a power rating of 15 kW / 20 HP, operates at three-phase 200-240 VAC, and is enclosed in an IP20 chassis. Part of the VLT EZ FC 321 Automation Drives by Danfoss, it incorporates an RFI Class A2 (C3) filter and a graphical local control panel for ease of use.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

132L4429 is a 15 kilowatts AC drive from Danfoss’s VLT FC 321 series. Tools needed for drive installation include lifting aids, drill, tape measure, screwdrivers, wire crimper and pliers. Items supplied with the unit vary with configuration. Operators must review information listed on the drive nameplate to identify its specifications, and conduct a visual inspection to ensure that the drive is undamaged. Information printed on the nameplate includes the type code, code, power rating, input voltage, output voltage, enclosure size, and certifications. Hazardous voltages on the drive can cause electric shock and even death. Therefore, only personnel with requisite skills should work on the drive. Before starting any maintenance activity, the motor must be stopped and the AC power to the drive must be disconnected. A wait time of 15 minutes after AC mains disconnection is required to allow DC-link capacitors to discharge fully.

Hot surface on the drive can cause serious burns. Therefore, appropriate precautions must be taken to prevent accidental contact. Weight of the 132L4429 drive is 52 lbs and its dimensions are 20.5 x 9.1 x 9.6 inches. Proper lifting equipment is necessary for preventing equipment damage and injury to working personnel. Use of the drive unit in explosive atmospheres is not permitted, and is only allowed when the unit is installed inside a cabinet that is located outside the explosive area. Proper cooling is necessary for safe and reliable drive operation. Danfoss recommends a minimum spacing of 7.8 inches on the top and bottom sides of the mounted drive. Side-by-side mounting of FC 321 drives is allowed. For this drive with 200 to 240 Volts AC input, the maximum cable size for mains and motor connections is 2 AWG.

Brake - Safe Stop
Brake Chopper
Coating Pcb
Not Coated
Enclosure
IP20 / Chassis
Gross Weight
24.39 kg
Lcp
Graphical Local Control Panel
Net Weight
20.69 kg
Power Rating
15 kW / 20 HP
Product Group
FC- VLT AutomationDrive EZ
Rfi Filter
RFI Class A2 (C3)
Vlt Series
321
Voltage
Three Phase 200-240 VAC
Volume
158.268 L

Frequently Asked Questions about 132L4429:

Q: How can you identify the drive?

A: A nameplate on the drive allows easy identification.

Q: What is the recommended wait time after power disconnection?

A: The recommended wait time after power disconnection is 15 minutes.

Q: Which communication interface is available on the drive?

A: An optional Ethernet card is installed on the unit.

Q: What is the frame size?

A: Frame size of the drive is B4.

Q: What is the operating power loss?

A: The power loss is 624 Watts.