4.94 based on 222 reviews

🙶 Wake Ind. did a great job with very fast service getting us a motor driver to repair our critical robot sy... 🙷

FC-202P7K5T2131X5673 Danfoss

Ask for Availability

Preparing your secure checkout page...

The Danfoss FC-202P7K5T2131X5673 is a drive from the VLT FC 202 AQUA Drives series with a power rating of 7.5 kW and supports three phase power input at 200 to 240 VAC. It has a continuous output current of up to 30.8 Amps, a maximum input current of 28 Amps, and delivers 10 horsepower. The drive operates efficiently at 0.96 and allows for a maximum motor cable length of 300 meters with unshielded cable.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The FC-202P7K5T2131X5673 is an AC variable-frequency drive produced by Danfoss for the VLT FC 202 AQUA Drives series. Designed for pump and fan duty in water and wastewater facilities, the unit converts three-phase mains power into a regulated output. This allows connected controllers to match motor speed to real-time flow demand, reducing mechanical stress on pumps and lowering energy use when full output is unnecessary.

This drive accepts supply voltages from 200 to 240 VAC on a three-phase circuit and is protected by a recommended 63 A pre-fuse. The maximum input current is 28.0 A, while the continuous output current is 24.2 A when heavy-overload operation is selected. Under normal-overload operation, the inverter can deliver up to 7.5 kW, which is equivalent to 10 HP of mechanical power at the motor terminals. Full-load efficiency reaches 0.96, so only a small fraction of the electrical energy is lost as heat during operation. Control wiring is rated for 28 V DC on the digital inputs and 40 mA on the digital outputs, supporting direct connections to typical PLC I/O cards without interposing relays. Shielded motor cabling may extend up to 150 m, while an unshielded cable may extend up to 300 m. These cable allowances provide flexibility when positioning the inverter at a distance from the connected pump or fan motor.

During continuous normal-overload service, the output current can rise to 30.8 A, generating an estimated heat dissipation of 310 W that must be removed through enclosure airflow. The electronics remain operational at surrounding temperatures up to 50 °C, provided that the required ventilation clearances are maintained around the drive. Installations at elevations up to 1000 m require no current derating. Above that elevation, the drive can continue operating at heights up to 3000 m when the available output current is reduced appropriately. Adequate airflow must be maintained throughout operation to prevent accumulated heat from affecting the inverter electronics and connected control wiring.

Cont. Output Current (ho)
24.2 A
Cont. Output Current (no)
30.8 A
Efficiency
0.96
Est. Power Loss (no)
310 W
Horse Power
10 HP
Mains Voltage
200 - 240 VAC
Max Altitude No Derating
1000 m
Max Altitude With Derating
3000 m
Max Ambient Temp
50 °C
Max Digital Input Voltage
28 V DC
Max Digital Output Current
40 mA
Max Input Current (no)
28.0 A
Max Pre-fuse
63 A
Max Shielded Motor Cable
150 m
Max Unshielded Motor Cable
300 m
Power Phase
Three Phase Power
Power Rating
7.5 KW
Product Group
VLT AQUA Drive
Series Identifier
202

Frequently Asked Questions about FC-202P7K5T2131X5673:

Q: What is the power rating of the FC-202P7K5T2131X5673 drive?

A: The VLT FC-202P7K5T2131X5673 drive supports a power rating of 7.5 kW.

Q: What is the mains voltage requirement for the FC-202P7K5T2131X5673?

A: Its input voltage range is from 200 to 240 VAC, suitable for medium-voltage environments.

Q: What is the maximum continuous output current for the FC-202P7K5T2131X5673?

A: The drive can handle a maximum continuous output current of 30.8 A with no overload.

Q: What is the horsepower rating of the FC-202P7K5T2131X5673?

A: This model provides a 10 horsepower output for your application needs.

Q: What is the maximum ambient temperature supported by the FC-202P7K5T2131X5673?

A: The FC-202P7K5T2131X5673 can operate at up to 50 °C ambient temperature.


Internal Product Review

  • ‘‘The FC-202P7K5T2131X5673 is a Danfoss VLT FC 202 AQUA drive built for three-phase power at 200 to 240 VAC. A 7.5 kW / 10 HP rating gives this unit solid capacity for water-handling applications, while 0.96 efficiency supports economical operation. Max unshielded motor cable reach of 300 m is a standout advantage for distributed installations.’’