The Danfoss FC-202P45KT6135N4885 is part of the VLT FC 202 AQUA Drives series and delivers a shaft output of 37 kW at heavy overload and 45 kW at normal overload. This three-phase drive achieves an efficiency of 0.98 and supports a maximum output current of 62 A. It operates at ambient temperatures up to 50 °C and allows shielded cable lengths up to 150 meters.
Internal Product Review
The FC-202P45KT6135N4885 is a Danfoss VLT FC 202 AQUA drive with 45 kW shaft output and 62 A nominal output current. An efficiency rating of 0.98 and frequency output up to 32 kHz support smooth, energy-conscious operation in demanding water and process applications. Support for 150 m shielded cable runs and 300 m unshielded cable runs makes the unit especially appealing for flexible installation layouts.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The FC-202P45KT6135N4885 is an AC variable frequency drive manufactured by Danfoss and offered in the VLT FC 202 AQUA Drives series, which is part of the VLT AQUA Drive product group. Designed for pump and fan operation in water and wastewater facilities, the drive converts fixed mains power into a controlled output that matches motor speed to hydraulic demand, delivering energy savings and steady process pressure. It performs closed-loop regulation when paired with flow, level, or pressure transmitters, enabling precise automation of filtration skids, booster stations, and aeration blowers.
The unit operates on three-phase power, drawing the supply through terminals sized for a minimum grounding conductor of 10 mm² and delivering an overall efficiency of 0.98. The inverter section can switch at frequencies up to 32 kHz, while command channels accept digital signals up to 28 V DC. Under normal duty, the output stage supplies 62 A, corresponding to a continuous shaft power of 45 kW; the heavy-overload profile allows 52 A and 37 kW for intermittent torque peaks. Motor leads may run 150 m with shielded cabling or 300 m with unshielded cabling, providing layout flexibility for remote pump halls. Internally, IGBT losses and ambient heat are managed so the unit can maintain its full rating at a surrounding temperature of 50 °C with airflow from the integral cooling fans.
The drive maintains full electrical capacity at elevations up to 1000 m and can continue operating with linear derating at elevations up to 3000 m. Upstream circuit protection supports a maximum prefuse rating of 150 A, helping protect the supply conductors and drive components during excessive current conditions. The line and motor terminals accept copper conductors with cross-sectional areas up to 50 mm², providing sufficient capacity for the applicable input and output connections.