FC-202P30KT2131U3268 Danfoss
Wake Industrial LLC is not an authorized distributor of this product.
The Danfoss FC-202P30KT2131U3268 is a VLT FC 202 AQUA Drives series variable frequency drive with a 30 kW power rating and 40 HP output. It operates on three phase 200 to 240 VAC mains voltage and supports a continuous output current of 115 Amps. The drive offers a maximum output frequency of 590 Hz, is rated for up to 41.4 kVA apparent power, and has an efficiency of 0.97.
Internal Product Review
The FC-202P30KT2131U3268 is a Danfoss VLT FC 202 AQUA drive with a 30 kW rating and 200-240 VAC input. Continuous output at 115 A and 0.97 efficiency give the drive strong throughput with impressive energy performance. A 5 ms control scan interval supports responsive regulation, and the 590 Hz maximum output frequency adds valuable application flexibility.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
Danfoss manufactures the FC-202P30KT2131U3268, an AC variable frequency drive in the VLT FC 202 AQUA Drives series. Designed for pump and fan regulation in water and wastewater facilities, the unit converts fixed three-phase mains power into variable output power that allows precise motor speed control and energy savings in fluid-handling processes. By integrating standard I/O and bus options, the drive can be installed in new systems or retrofits where coordinated automation of centrifugal equipment is required.
The drive supplies a continuous apparent power of 41.4 kVA, indicating the combined real and reactive load it sustains during steady operation. Its continuous output current of 115 A is the maximum current it can deliver to the motor terminals under rated thermal conditions. Compatibility with 200 – 240 VAC input power allows connection to low-voltage three-phase networks without step-up transformers. Reliable operation at temperatures up to 50 °C allows cabinet installation in hot utility rooms when applicable derating curves are observed. An efficiency of 0.97 limits conversion losses and supports compliance with IE2 energy-efficiency objectives.
Short-duration overloads are handled by an intermittent output current of 127 A, providing extra torque during pump startup or when clearing a valve blockage. Upstream protection is coordinated with a 160 A prefuse rating so supply conductors and breakers can be sized consistently. The control platform can generate carrier frequencies up to 590 Hz, enabling stable motor operation on high-speed centrifugal machines or permanent-magnet pumps. A permissible motor cable length of 150 m supports remote mounting of the drive outside wet areas while maintaining a reliable motor connection. The unit tolerates 95% relative humidity and completes each control loop every 5 ms, maintaining accurate flow regulation.