FC-202P22KT4131F6765 Danfoss
Wake Industrial LLC is not an authorized distributor of this product.
The Danfoss FC-202P22KT4131F6765 is part of the VLT FC 202 AQUA Drives series and offers a power rating of 22 kW with a 30 horsepower output. Designed for use on a three-phase 380 to 480 VAC mains voltage, it provides a continuous output of 30.5 kVA at 400 V and 31.9 kVA at 460 V. This drive can operate at ambient temperatures up to 50 °C and supports shielded motor cables up to 150 meters.
Internal Product Review
The FC-202P22KT4131F6765 is a Danfoss VLT FC 202 AQUA drive engineered for dependable pump and water-process control, with a 22 kW rating and three-phase power input. Operation across 380 - 480 VAC mains and ambient capability up to 50 °C supports stable integration in demanding industrial service. A maximum shielded motor cable length of 150 m adds installation flexibility, making the unit a strong choice for 30 HP drive applications.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The FC-202P22KT4131F6765 is an AC variable-frequency drive manufactured by Danfoss for the VLT FC 202 AQUA Drives series. It modulates induction motor speed in pump and fan systems used in water treatment and irrigation plants, where accurate flow regulation and soft starting protect mechanical equipment and reduce energy consumption. By converting fixed-frequency three-phase mains power into a controlled output waveform, the unit provides closed-loop flow or pressure control that adjusts motor torque according to process demand.
This model delivers a continuous power output of 22 kW, which corresponds to a motor output of 30 HP. The input section accepts a mains voltage range of 380–480 VAC, allowing direct connection to standard industrial power supplies without transformers. Protective coordination is supported by a maximum recommended pre-fuse rating of 63 A, while the analog output channel can drive instrumentation loads with an impedance of up to 500 Ω. Two transistor outputs provide status or alarm signaling with a maximum sourcing capacity of 40 mA. These connections allow the drive to communicate operating conditions to control relays, monitoring devices, and external automation equipment.
Full-load operation is available at elevations up to 1000 m above sea level, while reduced output allows operation at elevations up to 3000 m. The heat sink and control boards tolerate ambient temperatures up to 50 °C when cabinet airflow follows the manufacturer’s requirements. Motor leads can use shielded cable runs up to 150 m without exceeding limits associated with switching-frequency voltage drops. Unshielded motor cables can extend to 300 m when the installation permits their use. Proper separation of power and control wiring helps reduce electromagnetic interference in feedback signals and connected instrumentation. Adequate enclosure ventilation is required to remove heat from the drive during sustained operation in pump stations and similar industrial systems.