FC-202P1K1T4131G1976 Danfoss
Wake Industrial LLC is not an authorized distributor of this product.
The Danfoss FC-202P1K1T4131G1976 is part of the VLT FC 202 AQUA Drives series and has a power rating of 1.1 kW with three phase power input. It delivers a continuous input current of 2.7 A and operates at 380 to 480 VAC, supporting a maximum ambient temperature of 50 °C. With an efficiency of 0.96 and an IE2 energy efficiency class, it features a maximum relative humidity tolerance of 95% and supports up to 300 meters of unshielded motor cable.
Internal Product Review
The FC-202P1K1T4131G1976 is a Danfoss VLT FC 202 AQUA drive designed for three-phase power and 380 - 480 VAC mains. Efficiency of 0.96 and IE2 energy classification give this unit a notably economical operating profile in continuous-duty service. Support for 50 °C ambient temperature and 95% relative humidity makes this drive an excellent fit for demanding water-handling installations.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The FC-202P1K1T4131G1976 is a three-phase AC variable frequency drive produced by Danfoss within the VLT FC 202 AQUA Drives series. Designed for centrifugal pumps, aerators, and similar fluid-handling machines, the drive modulates motor speed to maintain flow or pressure while minimizing energy use in automated water and wastewater systems. Mains compatibility spans 380–480 VAC three-phase networks, and a 10 A pre-fuse protects the rectifier stage against short-circuit events.
It draws a continuous line current of 2.7 A, so supply conductors and protection devices can be sized for that steady load. At 460 V, this corresponds to an apparent power of 2.4 kVA, providing a clear basis for transformer and feeder planning. Overall conversion efficiency reaches 0.96, meaning only 4% of the incoming energy is dissipated as heat, which supports compact cabinet layouts. The inverter is rated for a mechanical output of 1.1 kW, equivalent to 1.5 HP, aligning it with small to medium pump motors used in booster stations. The unit meets IE2 energy-efficiency requirements, helping facilities document compliance with regional power-consumption targets.
Ambient service temperatures up to 50 °C are permitted without derating, and functional integrity is maintained in atmospheres containing up to 95% relative humidity. Cable management guidelines specify a ground conductor of 10 mm², disconnect wiring up to 6 mm², and line conductors up to 4 mm². Motor leads may extend up to 300 m in an unshielded installation or up to 150 m in a shielded installation when electromagnetic interference must be contained. Thermal losses are limited to 58 W, allowing simple forced-air cooling inside typical control enclosures. Mechanical durability is verified at a vibration test level of 1.0 g, supporting stable operation on wall-mounted or skid-mounted assemblies subjected to pump-induced vibration.