4.94 based on 222 reviews

🙶 a+ fast delivery 🙷

FC-202P18KT2131F1084 Danfoss

Ask for Availability
No Hidden Fees Rush or Credit Card
No Tariffs On US Orders

Internal Product Review

The FC-202P18KT2131F1084 is a Danfoss VLT FC 202 AQUA Drive designed for three-phase power at 18.5 kW. A 200 to 240 VAC mains range and 25 HP output make this drive a strong fit for demanding water and pump applications. Stable operation at ambient temperatures up to 50 °C is a standout advantage.

Sell Part
Have a part to sell?
Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The FC-202P18KT2131F1084 is a variable frequency drive produced by Danfoss for the VLT FC 202 AQUA Drives series. The unit converts fixed-frequency three-phase power into a programmable output that allows plant controllers to adjust pump and blower speeds in water-handling and HVAC processes. By regulating motor frequency, it can reduce energy consumption and provide gentle ramping during start and stop sequences in industrial automation.

The drive delivers 25 HP and accepts an input of 200 – 240 VAC. It supports continuous operation at temperatures up to 50 °C and altitudes up to 1000 m without derating. The inverter synthesizes output frequencies with 12-bit resolution and reaches 32 kHz, helping reduce audible motor noise. One analog channel with 8-bit resolution and 500 Ω impedance and two digital pulse outputs share operating data with external controls. Digital inputs tolerate 28 V DC, while transistor outputs can source 40 mA for relays or indicators. The drive withstands vibration of 1.0 g, supporting mechanical stability in typical plant installations. Shielded motor cable can extend up to 150 m, allowing the drive to remain inside dry switchgear while serving remotely installed equipment. Its rated electrical power is 18.5 kW, making it suitable for midrange centrifugal pumps and similar loads.

System protection and electromagnetic compatibility are addressed at the input and output stages. Upstream circuit breakers can be selected with a maximum prefuse rating of 125 A to clear short-circuit faults quickly. With a 36 m motor lead, the output pulses reach a peak voltage of 0.608 kV and have a voltage rise rate of 1.993 kV/µs. These values assist with the selection of suitable surge filters and motor insulation classes. The drive maintains full performance when connected to balanced three-phase lines. Its control terminals and pulse outputs provide direct interfaces for automation equipment, reducing the need for separate signal-conversion hardware.

Analog Output Load
500 Ω
Analog Output Resolution
8 bit
Analog Outputs
1
Digital Pulse Outputs
2
Frequency Output Resolution
12 bit
Horse Power
25 HP
Mains Voltage
200 - 240 VAC
Max Altitude Without Derating
1000 m
Max Ambient Temperature
50 °C
Max Digital Input Voltage
28 V DC
Max Digital Output Current
40 mA
Max Frequency Output
32 kHz
Max Motor Cable, Shielded
150 m
Maximum Pre-fuses
125 A
Peak Voltage At 36 M
0.608 kV
Power Phase
Three Phase Power
Power Rating
18.5 KW
Product Group
VLT AQUA Drive
Series Identifier
202
Vibration Test
1.0 g
Voltage Rise Rate At 36 M
1.993 kV/μsec

Frequently Asked Questions about FC-202P18KT2131F1084:

Q: What is the horsepower rating of the Danfoss FC-202P18KT2131F1084 drive?

A: The Danfoss FC-202P18KT2131F1084 is rated for 25 HP, making it suitable for medium power applications.

Q: What is the allowable mains voltage for the FC-202P18KT2131F1084 drive?

A: This drive supports a mains voltage range of 200 to 240 VAC, compatible with low to medium voltage installations.

Q: How long of a shielded motor cable can be used with the Danfoss FC-202P18KT2131F1084?

A: The maximum cable length for shielded motor cables is 150 meters for this model.

Q: How many analog outputs does the Danfoss FC-202P18KT2131F1084 offer?

A: The FC-202P18KT2131F1084 includes one analog output, suitable for basic analog control needs.

Q: What is the maximum ambient temperature for the FC-202P18KT2131F1084 drive?

A: This drive can operate at a maximum ambient temperature of 50 °C without derating.

Motion Industries logo
3M logo
IBM logo
Gexpro Logo
Caterpillar logo
NASA logo
Ford logo
Vallen logo