131B9006
Wake Industrial LLC is not an authorized distributor of this product.
MPN: FC-202P15KT4E21H2XGCXXXSXXXXAXBXCXXXXDX
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
-
In-Stock, Ships in 3 Days
The Danfoss 131B9006 drive is a part of the VLT FC 202 AQUA Drives series and supports +10 V DC output for analog references. It includes two programmable relays, each with a max AC resistive load of 240 V AC and 2 A. The relay terminals support wire sizes of 0.25–1.5 mm² with a tightening torque of 0.5 Nm.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
Danfoss 131B9006 belongs to the VLT FC 202 AQUA Drive family, which is intended to be used in water and wastewater facilities where energy efficiency and flexible I/O are required.
This model incorporates advanced relay capability to meet a variety of operational needs in pump, fan, and process control systems. The drive gives an analog output voltage of +10 V DC with a maximum current of 15 mA, which is appropriate to use as analog reference signals. It contains two programmable relays that can each carry an AC load and a DC load of varying ratings based upon application. Relay 1 is able to carry up to 240 V AC at 2 A resistive loads and 60 V DC at 1 A resistive DC loads. For inductive loads, it is relatively lower, at only 24 V on the DC side or 240 V on the AC, lasting only 0.1 A or 0.2 A, respectively.
Relay 2 offers an additional function by opening up to 400 V AC at 2 A in resistive circuits, providing reliable performance in standard applications. It also carries 80 V DC at 2 A in DC circuits and lower ratings in inductive circuits to ensure safe and reliable performance. To ensure safe and dependable wiring, the relays take terminal wire sizes 0.25-1.5 mm² (24-16 AWG) and have a tightening torque of 0.5 N m (4.4 lb-in). The stripping length is given as 8-9 mm (0.31-0.35 in), which guarantees stable and safe connections. NO/NC contacts have a minimum terminal load of 24 V DC at 10 mA or 24 V AC at 20 mA, ensuring reliable signal quality throughout low-power situations.
Frequently Asked Questions about 131B9006:
Q: What series does the 131B9006 belong to?
A: The 131B9006 is part of the Danfoss VLT FC 202 AQUA Drive family, made for water and wastewater applications.
Q: What analog output does the 131B9006 provide?
A: The 131B9006 provides a +10 V DC analog output with a maximum current of 15 mA, suitable for analog reference signals.
Q: How many programmable relays does the 131B9006 include?
A: The 131B9006 includes two programmable relays, each capable of handling both AC and DC loads with varying ratings.
Q: What are the maximum AC and DC ratings of Relay 2 in the 131B9006?
A: Relay 2 can switch up to 400 V AC at 2 A in a resistive circuit, or 80 V DC at 2 A in a DC circuit.
Q: What terminal wire sizes are supported by the 131B9006 relays?
A: The relays accept terminal wire sizes from 0.25–1.5 mm² (24–16 AWG), with a tightening torque of 0.5 N m (4.4 lb-in).