VLT6005HT4C54STR3DLF00A00C0

Ask for Availability

Preparing your secure checkout page...

The VLT6005HT4C54STR3DLF00A00C0 is a high-performance HVAC drive offering a continuous output current of 4.9A at 525-550V. Built by Danfoss as part of the VLT 6000 HVAC Drives series, it delivers a typical shaft output power of 4 HP. The drive supports an output frequency range of 0-120 Hz and weighs 9 kg in its IP20 enclosure.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The Danfoss designed VLT6005HT4C54STR3DLF00A00C0 unit stands out as a prime choice for demanding automation applications. Operating with a line voltage of 3 x 525/550/575/600 V ±10%, it accommodates a range of input scenarios to ensure reliable performance in various setups. Also, supporting a frequency of 48-62 Hz ±1%, this component is not only versatile but is also stable across widely used utility frequencies. Thus, the product is suitable for European regions as well as other global locations.

Utilizing this industrial-grade drive also brings to the table dependable power handling, as exhibited through the continuous output current rating of 4.9 A (at 525-550 V) and 4.5 A (at 551-600 V). Also, the intermittent overload current ratings are 7.8 A (at 525-550 V) and 9.8 A (at 551-600 V). The continuous apparent power capacity of 5.0 kVA (at 525 V) strengthens its ability to drive loads without performance compromise. This commercial unit's output voltage capability runs from 0 to 100% of the supply voltage, allowing for seamless integration with a broad variety of standard motor systems. Its efficiency, rated at 0.96, maintains that operational costs remain in check and that energy waste is minimized over the long haul.

Danfoss’ VLT6005HT4C54STR3DLF00A00C0 controller also maintains remarkable temperature resilience with an operational limit of 45°C, allowing it to adapt to heat-prone environments consistently. Its weight is also on the lower side, weighing 9 kg (IP20) or 13.5 kg (IP54), facilitating simpler installation and transportation. Moreover, it has a maximum pre-fuse of 25 A, offering a safety buffer for transient surges. This item with a power loss capacity at maximum load of 172 W, thus maintaining efficiency while facilitating demanding loads. These high-performing specifications and safety aid in maintaining the drive effectiveness and security with this unit.

Ambient Temperature Max
45°C (Full operation)
Continuous Apparent Power
5.0 kVA (525 V)
Continuous Output Current
4.9 A (525-550 V), 4.5 A (551-600 V)
Efficiency At Rated Current
0.96
Enclosure Type
IP20/Chassis
Intermittent Overload Current
7.8 A (525-550 V), 9.8 A (551-600 V)
Line Voltage
3 x 525/550/575/600 V +-10%
Max Pre-fuse (ul)
25 A
Output Frequency
0-120 Hz, 0-1000 Hz
Output Voltage
0-100% of supply voltage
Power Loss At Max Load
172 W
Rated Motor Frequency
50/60 Hz
Supply Frequency
48-62 Hz +-1%
Typical Shaft Output Power
4 HP, 3 kW
Weight
9 kg (IP20), 13.5 kg (IP54)

Frequently Asked Questions about VLT6005HT4C54STR3DLF00A00C0:

Q: What is the output power of the VLT 6000 HVAC VLT6005HT4C54STR3DLF00A00C0 drive?

A: It delivers up to 4 HP (3 kW) of shaft output power that makes it accessible for medium capacity HVAC motors. This ensures efficient operation without oversizing the drive.

Q: How does this Danfoss’ VLT6005HT4C54STR3DLF00A00C0 handle overload conditions?

A: The motor can manage intermittent overload currents of up to 7.8 A at 525–550 V and 9.8 A at 551–600 V. This further allows it to handle short bursts of extra demand.

Q: What is the maximum output frequency of Danfoss’ VLT6005HT4C54STR3DLF00A00C0 device?

A: The device supports output frequencies from 0–120 Hz in standard mode and up to 1000 Hz for specialized applications.

Q: How efficient is this Danfoss HVAC model?

A: The VLT6005HT4C54STR3DLF00A00C0 operates at 96% efficiency at rated current, thus reducing energy waste and operating costs. This efficiency value makes it a cost-effective option for long term use.

Q: What voltage supply does this HVAC motor require to operate?

A: The VLT6005HT4C54STR3DLF00A00C0 operates on a voltage supply rating of 3 × 525/550/575/600 V AC ±10% at 48–62 Hz, providing compatibility with high- voltage industrial systems.


Internal Product Review

  • ‘‘Part of the Danfoss’ VLT 6000 HVAC Drives lineup, the variant VLT6005HT4C54STR3DLF00A00C0 works well in high voltage HVAC systems. Providing 3 kW output with 96% efficiency, it can handle overloads up to 9.8 A without faltering. The drive’s compact IP20 chassis create integration straightforward for demanding and space conscious installations.’’

Motion Industries logo
3M logo
IBM logo
Gexpro Logo
Caterpillar logo
NASA logo
Ford logo
Vallen logo