VLT6005HT4B20STR3DLF00
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
-
In-Stock, Ships in 3 Days
The Danfoss VLT6005HT4B20STR3DLF00 is part of the VLT 6000 HVAC Drives series and features a compact NEMA 1/NEMA 12 enclosure. This drive delivers a typical shaft output power of 5 HP, a power output of 7.2 kVA, and an efficiency of 96%. It has a maximum input current of 9.1 amps and weighs 21 lbs for the NEMA 1 model.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The VLT6005HT4B20STR3DLF00 is a frequency converter. Its manufacturer is Danfoss, a Danish supplier of automation solutions for industrial applications. The converter is compatible with AC mains that provide 380 to 460 Volts AC. Its maximum input current value is 7 Amps rms at 380 Volts and 6 Amps at 460 Volts. For input power, Danfoss recommends using AWG 10 cables (4 mm2 cross-section). Input efficiency of the converter is 0.96. The weight of this IP20 rated converter is approximately 8.5 kilograms. The peak power loss at maximum load is 139 Watts. The converter supplies variable AC output to the connected motor. The output current at 380 to 440 Volts is 7.2 Amps. For 60 seconds, the output current can rise to 7.9 Amps. The output current is 6.3 Amps at 441 to 460 Volts.
It can rise to 6.9 Amps for 60 seconds. Power output of the VLT6005HT4B20STR3DLF00 drive is 5.2 kVA at 440 Volts and 5 kVA at 460 Volts. The typical shaft output is 3 kilowatts (5 Horsepower). The maximum cable size for the motor cable is 4 AWG. The converter has a bookstyle design. Its dimensions are 395 x 130 x 260 millimeters. The only allowed installation orientation for the converter is vertical. Side by side installation is allowed. Operators must ensure that the ambient temperature does not exceed 45 ⁰C. The minimum spacing on the top and bottom sides of the unit must be at least 100 millimeters. The product documentation mentions several safety precautions for converter use. These include disconnecting mains power before performing repairs, providing proper safety earthing, using motor overload protection, and following ESD precautions for converter safety.
Frequently Asked Questions about VLT6005HT4B20STR3DLF00:
Q: What is the protection class of the housing?
A: Protection class of the housing is IP20.
Q: Is a control panel available on the unit?
A: A local control panel is available on the unit.
Q: What is the maximum ambient temperature limit?
A: The ambient temperature limit for rated operation is 45 ⁰C.
Q: What is the power loss at maximum load?
A: The power load at maximum load is 139 Watts.
Q: Is the drive certified?
A: The drive is certified by CE and cULus.