The 178B0237 drive from Danfoss weighs 8.9 kilograms, supports three-phase operation, and features a mains voltage input range of 380-480V at 50/60Hz. As part of the VLT 6000 HVAC Drives series, it is specifically designed for HVAC applications and comes with an IP20 enclosure class for reliable performance.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

This 178B0237 HVAC drive’s control panel consists of a display and a keypad. The drive comes with a preset protection against overload of the motor. This product features improved speed regulation. The device facilitates mounting near another drive. This unit’s RFI filter complies with EN 55011 Class A1 specifications if the screened motor cable is 150 m long. Its PID regulator allows two feedback signals to be connected. The drive comes in a user-friendly design.

This product portrays high starting torque. The device highlights the local speed of the drive on its graphical display. This unit comprises a flying start function. It supplies the motor with variable frequency plus voltage. The drive’s automatic energy optimization function is activated by default. This product regulates the pressure constantly in a water supply system. The device’s ramp time varies from 1s to 3600s. This unit’s programmable pulse inputs have a maximum frequency based on the terminals they are associated with. Its 24 VDC power supply and the analog inputs have the same potential.

The drive’s minimum ambient temperature at reduced performance is -10 °C. This product executes a controlled deceleration when a mains fault is triggered. The device’s installation should ensure its proper cooling through the circulation of air. The unit requires adequate clearance at its top and bottom to release the cooling air. It supports flange-by-flange mounting. The HVAC drive’s installation is possible only on a flat surface. This product’s motor cables and control cables should be separated by at least 20 cm. The device can’t be used with Type A ELCB relays. This unit’s RFI switch should not be operated when the drive is actively connected to the mains. It uses braided screened cables as its control cables.

Dedicated Application
HVAC
Enclosure Class
IP20
Enclosure Type
Bookstyle
Fieldbus Option
Profibus DP
Gross Weight
9.2 kg
Mains Voltage U(in)
380-480V +/-10% 50/60Hz
Net Weight
8.9 kg
Phase
Three Phases
Product Group
VLT
Vlt Series
6000

Frequently Asked Questions about 178B0237:

Q: What is the function of the RFI switch of the 178B0237 drive?

A: The RFI switch of the 178B0237 drive connects the capacitors to the earth galvanically.

Q: Which terminals of the 178B0237 drive should be short circuited to carry out a high-voltage test?

A: The U, V, W, L1, L2, and L3 terminals of the 178B0237 drive should be short circuited to carry out a high-voltage test.

Q: What type of motor cables does the 178B0237 drive support?

A: The 178B0237 drive supports braided screened motor cables.

Q: Why should the serial communication cables of the 178B0237 drive be fitted with cable clamps?

A: The serial communication cables of the 178B0237 drive should be fitted with cable clamps for the best possible electrical contact.

Q: How are small-size motors connected with the 178B0237 drive?

A: Small-size motors connected with the 178B0237 drive using a star connection.