195N1082
Wake Industrial LLC is not an authorized distributor of this product.
MPN: VLT2840PT4B20SBR0DBF30A00C0
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
-
In-Stock, Ships in 3 Days
The 195N1082 is a compact drive weighing just 0.9 kg, designed exclusively for vertical mounting with an IP20 enclosure rating. Manufactured by Danfoss, it is part of the VLT 2800 Low Voltage Drives series and supports a maximum voltage of 480 V AC. The drive features an RFI 1B filter for excellent performance.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The 195N1082 low-voltage drive by Danfoss has an adjustable frequency. This drive might trigger unfavorable situations with an improper installation. The product has no factory setting for protection against motor overload. This device features higher than 3.5 mA ground leakage currents. The unit’s voltage inputs must be disconnected from load sharing through its DC bus. It can be serviced only after four minutes of removing its input power. This drive portrays a 5 HP power rating and a 200 V to 240 V voltage rating.
The product needs no side cooling and can be installed side-by-side. This device supports a free mounting position. The unit is installed in an enclosure at all times. Its 24-hour average temperature should not be exceeded. The drive’s service life gets reduced without applicable derating. This product needs at least 100 mm clearance at its fan inlet and outlet. The device must always be grounded in compliance with local safety guidelines. This unit may fail to comply with a few EMC/RFI requirements when unshielded cables are used. It is possible to install multiple drives in a single control cabinet by using the metal cabinet backplate as a joint ground reference plate.
This low-voltage drive’s electrical contact with the metal control panel must be ensured by using the drive installation screws, conductive fasteners, and lock washers. The product may generate electrical noise when its ground potential is different from that of the PLC. This device houses an RFI filter that cannot be connected to an IT mains/AC line system or a grounded DELTA system. The unit should encompass an LC filter at its output when it is used with a motor without phase insulation. It has an electronic thermal relay.
Frequently Asked Questions about 195N1082:
Q: How many digits are highlighted on the LED display of the 195N1082 drive?
A: Six digits are highlighted on the LED display of the 195N1082 drive.
Q: How many output data can be continuously displayed on the 195N1082 drive?
A: Only one output data can be continuously displayed on the 195N1082 drive.
Q: How can the 195N1082 drive be switched between auto and hand operational modes?
A: The 195N1082 drive can be switched between auto and hand operational modes by pressing the Change Data key.
Q: How are warnings and alarms highlighted in the LED display of the 195N1082 drive?
A: Warnings and alarms are highlighted in the LED display of the 195N1082 drive as a numerical code.
Q: What should the voltage of the 195N1082 drive match with?
A: The voltage of the 195N1082 drive should match with that of the associated motor and power line.