131Z9199
Wake Industrial LLC is not an authorized distributor of this product.
MPN: VLT2815PS2B20SBR1DBF00A00C1
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
-
Available
The 131Z9199 is a low voltage drive with a rated mains voltage range of 200-480 V and a maximum rated current of 16 A. Manufactured by Danfoss, it belongs to the VLT 2800 Low Voltage Drives series and features an IP20 enclosure rating. This 3.8 kg drive supports vertical mounting.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
131Z9199 is a Danfoss VLT 2800 series AC drive. Its input voltage range is 200 to 240 Volts. The drive can operate with single-phase or three-phase input. Its motor output is 1.5 kilowatts (2 Horsepower). Danfoss has designed the unit for process control applications. It is primarily used a motor control device. It achieves this function by producing variable AC output. When used with single-phase systems, it draws 15.2 Amps continuous current and 24.3 Amps peak current (60 seconds). When used with three-phase systems, it draws 7.6 Amps continuous current and 12.1 Amps peak current (60 seconds). Properly sized cables are essential for safe power delivery. Undersized cables can get overheated, causing equipment damage, and pose a fire hazard. The recommended line cable size for this drive is 4 mm2 (10 AWG).
The 131Z9199 drive only delivers 3-phase output. Its continuous output is 6.8 Amps and the peak output is 10.8 Amps (60 seconds). At 230 Volts, the output power is 2.7 kVA. The motor cable size recommended by Danfoss is 4 mm2 (10 AWG). The AC drive has a rated efficiency of 95%. During operation, it loses approximately 94 Watts as heat. The IP20 housing does not fully protect against dust or water. It should ideally be mounted inside a cabinet with robust ingress protection. The drive weighs 2 kilograms. Its approximate dimensions are 200 x 75 x 168 millimeters. A parameter list, quick setup guide, and operating instructions are supplied with the drive unit. A data sheet is also available on order. Proper ventilation is important for drive cooling. At least 4 inches (100 millimeters) of spacing must be provided above and below the drive.
Frequently Asked Questions about 131Z9199:
Q: What is the power loss at max load?
A: The power loss at max load is 94 Watts.
Q: What is the drive efficiency?
A: The drive efficiency is 95%.
Q: What is the max motor cable size?
A: The max motor cable size is 10 AWG.
Q: What is the max line cable size?
A: The max motor line cable size is 10 AWG.
Q: Can the drive operate with single-phase input?
A: The drive can operate with single-phase input.