NXP00136A5L0SSSA1AF00CP00
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The NXP00136A5L0SSSA1AF00CP00 drive offers a mains voltage range of 380-500 V, a nominal input current of 5.6 A, an enclosure class of MF4/IP21, IP54, and weighs 5 kg. Part of the VACON NXP Air Cooled Drives series by Danfoss, it supports motor shaft power up to 3 kW and features compact dimensions of 128x292x190 mm.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The Danfoss NXP00136A5L0SSSA1AF00CP00 frequency converter is part of the VACON® NXP Air-Cooled series. It is designed for accurate speed and torque control in industrial automation tasks. This unit uses a forced air cooling mechanism and is housed in a frame size FR06. It supports both wall-mounted and enclosed IP54 installation types.
The NXP00136A5L0SSSA1AF00CP00 frequency converter is compatible with induction motors and permanent magnet motors. This allows flexibility in multi-motor environments. The input voltage range is 3-phase 525-690 VAC with a ±10% tolerance. It also supports DC input between 640 VDC and 1100 VDC. The rated output current for this model is 13 A. It operates within a switching frequency range of 1-16 kHz. This configuration does not include an internal brake chopper. The power factor of the NXP00136A5L0SSSA1AF00CP00 frequency converter at rated load is approximately 0.98. The I/O options are provided via Slot A. This includes 6 digital inputs, 2 digital outputs, 2 analog inputs, and 1 analog output. The slot also includes a +10 V reference and a +24 V auxiliary supply. Slot B contains 2 relay outputs with changeover contact (NO/NC). Slot C is empty and reserved for expansion. Slot D comes factory-fitted with a PROFINET fieldbus module. Slot E is also available for optional interface components.
The operating temperature range of the NXP00136A5L0SSSA1AF00CP00 frequency converter is -10 °C to +50 °C without derating. Above +50 °C, power derating is required. It supports installation at altitudes up to 1000 m without derating and up to 4000 m with applied derating. The precise load of the unit measures about 18.5 kg. The drive incorporates key electrical safety features to protect both equipment and operators. These include Safe Torque Off (STO) to cut motor power instantly and Safe Stop 1 (SS1) for controlled halting.
Frequently Asked Questions about NXP00136A5L0SSSA1AF00CP00:
Q: How does NXP00136A5L0SSSA1AF00CP00 manage multi-motor flexibility?
A: The NXP00136A5L0SSSA1AF00CP00 frequency converter supports both induction and permanent magnet motors. This enables seamless adaptation across variable industrial motor types and load profiles.
Q: What overload capacity does NXP00136A5L0SSSA1AF00CP00 provide?
A: The NXP00136A5L0SSSA1AF00CP00 frequency converter handles 150% overload for up to 60 seconds. This allows reliable torque bursts during demanding acceleration or disturbance scenarios.
Q: How does NXP00136A5L0SSSA1AF00CP00 support modular control?
A: With populated I/O in Slot A and relays in Slot B, NXP00136A5L0SSSA1AF00CP00 frequency converter offers base-level modularity. The expansion options in Slot C and E increase system adaptability.
Q: What fieldbus options are available in NXP00136A5L0SSSA1AF00CP00?
A: The NXP00136A5L0SSSA1AF00CP00 frequency converter includes a factory-mounted PROFINET module. It also supports additional protocols such as CANopen, PROFIBUS DP, and EtherNet/IP via optional cards.
Q: How does NXP00136A5L0SSSA1AF00CP00 ensure motor thermal protection?
A: The model integrates ATEX-certified thermistor inputs to detect overtemperature events. This enables safe shutdown routines when abnormal heating is detected at the motor terminals.