4.95 based on 202 reviews

🙶 I have always received exceptional service and support in my many years of working with Wake Industrial. 🙷

080G0034 Danfoss

Available, Ships in 1-2 weeks
No Hidden Fees Rush or Credit Card
No Tariffs On US Orders

Internal Product Review

The 080G0034 is a Danfoss MCX programmable controller with 8 analog inputs and 8 digital inputs. Opto-insulated RS485 communication and IP40 front-cover protection support dependable panel integration in control applications. Eight relay outputs with a 32 A total relay load limit make the unit a very capable choice for demanding machine control.

Sell Part
Have a part to sell?
Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The 080G0034 programmable logic unit is supplied by Danfoss within the MCX Programmable Controllers series. As a compact controller, it combines discrete, analog, and communication resources to execute user logic for HVAC, pumping, or general automation tasks. It collects field signals, processes them with embedded programming, and operates onboard relays or analog channels so that connected equipment follows predetermined sequences. The integrated resources allow the controller to manage several types of field devices without requiring separate signal-processing modules.

The device operates from 24 V AC with a ±15% tolerance, and its circuitry draws up to 17 VA when energized by alternating current or 10 W from a direct-current source. Signal acquisition is handled by 8 analog inputs that accept temperature, pressure, or potentiometer references. The controller has 4 voltage-type analog outputs, each of which supports a load resistance of at least 1 kΩ and produces 6.8 V under open-circuit conditions. Eight digital inputs, each limited to 5 mA, monitor contact closures. Two PWM or PPM channels provide variable-duty control signals for compatible transducers. An optically isolated RS485 interface connects the controller to supervisory equipment. The front cover has an IP40 rating, providing protection against access by solid objects larger than 1 mm.

The output stage controls electromechanical loads through eight installed relays. Two relays are intended for high-inrush applications and have a continuous rating of 16 A. Their contacts tolerate surge currents up to 80 A for 20 ms when large inductive devices are first energized. The combined current across all relays must not exceed 32 A, which helps keep circuit-board traces and connectors within their operating limits. The remaining standard relays switch lighter circuits, including fans, pumps, valves, or alarm indicators. All switching hardware is installed on one compact board, reducing the amount of separate equipment required inside a distributed control box.

Analog Inputs
8
Analog Output Minimum Load
1 kΩ
Analog Output Open-circuit Voltage
6.8 V
Analog Voltage Outputs
4
Digital Inputs
8 (5 mA)
High-inrush Relays
2 (16 A)
Max Power Consumption (ac)
17 VA
Max Power Consumption (dc)
10 W
Protection Class
IP40 (front cover)
Pwm/ppm Outputs
2
Relay Inrush Current (c1,c2)
80 A (20 ms)
Relay Outputs
8
Rs485 Interface
Yes (opto-insulated)
Supply Voltage (ac)
24 V AC (±15%)
Total Relay Load Limit
32 A

Frequently Asked Questions about 080G0034:

Q: How many analog inputs does the Danfoss 080G0034 controller offer?

A: This controller includes eight analog inputs for precise sensor integration.

Q: What is the current rating for the high-inrush relays on the 080G0034?

A: The 080G0034 features high-inrush relay outputs rated at 16 A each, making it suitable for applications with large startup currents.

Q: What is the required supply voltage for the Danfoss 080G0034 MCX controller?

A: The controller operates with a supply voltage of 24 V AC, accommodating a variation of ±15%.

Q: How many digital inputs are available and what is their rating on the 080G0034?

A: This unit provides 8 digital inputs, each rated for 5 mA, supporting various logic and sensor connections.

Q: What is the maximum power consumption of the Danfoss 080G0034 controller?

A: The maximum power consumption is 17 VA for AC operation and 10 W for DC operation, ensuring energy-efficient performance.