4.95 based on 202 reviews

🙶 First-time customer with Wake Industrial. The ordering process was completely seamless. The part that we o... 🙷

132H2264 Danfoss

Ask for Availability

Preparing your secure checkout page...

The Danfoss 132H2264 is part of the MCD Soft Starters series and is rated for heavy duty with a current rating of 240 Amps and a motor power of 200 HP. It features an internal bypass contactor, operates at 480 V AC three phase power, and has an enclosure rating of NEMA 12.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The 132H2264 soft starter is produced by Danfoss within the MCD Soft Starters series. It is a solid-state motor controller that gradually increases stator voltage so large induction motors reach full speed without the inrush current seen in direct-on-line starting. By managing acceleration and deceleration profiles, the unit reduces mechanical shock to drive trains, lowers peak electrical demand, and improves uptime in automated conveyors, pumping stations, and fan systems that require smoother starting behavior in continuous-duty industrial environments.

Its control circuit operates at 120 VAC, allowing common panel supplies to energize the logic and trigger circuitry. The power section is rated for 240 A, so it can deliver sufficient current for medium-to-large motors during controlled acceleration. An internal bypass contactor closes after the voltage ramp, transferring the running load to a low-loss path and minimizing heat inside the starter. For plant areas containing airborne oil or light dust, the assembly has a NEMA 12 enclosure that helps protect internal components from contamination and non-corrosive liquid exposure. Mains terminals accept 480 V AC, matching typical North American distribution lines for high-horsepower drives.

This model is intended for intensive applications, and its heavy-duty rating confirms that it tolerates frequent starts with elevated current multiples. When paired with a motor up to 200 HP, the device limits torque transients that would otherwise strain couplings. It is intended for three-phase power, coordinating all three line voltages through phase-controlled SCRs to keep the motor's magnetic field balanced during voltage ramping and deceleration. Because the starter is supplied as an enclosed unit, wiring, heat sinks, and bypass components are mounted inside a finished cabinet, simplifying installation in MCC sections or standalone wall mounts.

Bypass Type
Internal Bypass Contactor
Control Voltage
120 VAC
Current Rating
240 A
Duty Rating
Heavy Duty
Enclosure Rating
NEMA 12
Enclosure Type
Enclosed
Mains Voltage
480 V AC
Motor Power
200 HP
Phase Power
Three Phase Power
Product Group
VLT Soft Starter MCD

Frequently Asked Questions about 132H2264:

Q: What is the control voltage required for the Danfoss 132H2264 soft starter?

A: The Danfoss 132H2264 supports a control voltage of 120 VAC.

Q: What type of bypass contactor is included in the 132H2264 soft starter?

A: This model features an internal bypass contactor to help reduce energy loss during operation.

Q: What is the maximum current rating of the Danfoss 132H2264?

A: The 132H2264 soft starter has a current rating of 240 A for heavy duty applications.

Q: What enclosure rating does the Danfoss 132H2264 soft starter have?

A: The enclosure has a NEMA 12 rating, providing protection against dust and dripping water.

Q: What is the maximum motor power supported by the 132H2264 at 480 V AC?

A: This model is rated for motors up to 200 horsepower on 480 V AC three-phase power.


Internal Product Review

  • ‘‘The Danfoss 132H2264 is a heavy duty MCD soft starter featuring an internal bypass contactor and a 120 VAC control voltage, making it suitable for demanding industrial applications. With a 240 A current rating and compatibility with 480 V AC three-phase power, this unit delivers strong performance for motors up to 200 HP. Its NEMA 12 enclosed design ensures reliable operation in harsh environments.’’