132H2226 Danfoss
Wake Industrial LLC is not an authorized distributor of this product.
MPN: MCD60275CT5S2X00CV2
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The Danfoss 132H2226 belongs to the MCD Soft Starters series and is designed for three phase power applications. This soft starter offers a current rating of 275 Amps and supports motors up to 150 hp at 480 V. It features an IP00 rating and weighs 12.8 kilograms.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The 132H2226 belongs to the MCD Soft Starters series manufactured by Danfoss for use with induction motors in industrial automation. By adjusting the motor's voltage during ramp-up and ramp-down, this electronic starter limits mechanical stress on gearboxes, pumps, and conveyors during acceleration. It also cuts the inrush current that would otherwise load upstream switchgear and transformers during motor starting.
The unit supports motors up to 150 hp when the supply is 480 V AC. Its full-load current capacity is 275 A, and the IEC duty 3.5-15 : 50-6 rating indicates the thermal allowance for short-term starts and stops. Danfoss packages the power section in a frame size 2 housing, allowing panel builders to select matching busbar spacing and cooling clearances. Operation is limited to three-phase power; the starter synchronizes the three output SCR pairs to maintain balanced phase angles. An enclosure classification of IP00 means all live parts require installation inside a protected cabinet, so external finger or drip protection must come from the surrounding panel. No earth conductor is mandated because the design lists the ground connection as not required, simplifying field wiring in retrofit situations.
Power terminations use an M12 bolt, and the recommended tightening level is 66 Nm to keep the copper lugs from loosening under thermal cycling. There is 12.8 kg of mass in the assembly, so vertical mounting surfaces must accommodate that static load. The control scheme relies on external contactors because there is no internal bypass; once run-time current stabilizes, a separate bypass device can be energized to reduce heat in the SCR stack. The product group is VLT Soft Starter MCD, and its terminals are supplied with plain hardware; users must provide any optional protective shrouds or insulated boots required by local codes.
Frequently Asked Questions about 132H2226:
Q: What is the current rating of the Danfoss 132H2226 soft starter?
A: The Danfoss 132H2226 soft starter has a current rating of 275 A, suitable for high-powered applications.
Q: What is the maximum horsepower supported by the 132H2226 at 480 V?
A: This soft starter is rated for up to 150 hp when used with a 480 V power supply.
Q: Does the Danfoss 132H2226 soft starter include an internal bypass?
A: An internal bypass is not included with the 132H2226 model.
Q: What type of power system is the 132H2226 soft starter designed for?
A: The 132H2226 model is designed for three-phase power systems.
Q: What IP rating does the 132H2226 soft starter have?
A: The Danfoss 132H2226 soft starter has an IP00 rating, meaning it is not protected against solid objects or liquids.