The Danfoss 084B4057 is part of the AK-CC55 Case Controllers series and is designed for DIN rail mounting. It features 6 analog inputs, 3 digital inputs, 6 digital outputs, and 9 application switches. The controller provides a relay resistive load capacity of 8 Amps and supports a maximum AKV output current of 0.5 Amps.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The 084B4057 controller is produced by Danfoss within the AK-CC55 Case Controllers series and is intended for supervisory regulation of refrigerated display or storage cases in automated food retail installations. Acting as a dedicated case controller, it processes temperature, defrost, fan, and light commands to maintain stable product conditions while interfacing with higher-level building management systems. In industrial automation applications, it combines sensing, local logic, and relay actuation in a single DIN-rail module that replaces discrete thermostats and time clocks.

Six analog inputs accept probe signals for case temperature, suction line temperature, and defrost termination, while three digital inputs monitor door or alarm contacts. Nine application switches allow parameter selection without software. The controller powers electronic expansion valves through an AK-V output rated at a maximum of 0.5 A, delivering up to 1 × 20 W at maximum output when supplied by 115 V AC or 2 × 20 W at maximum output when supplied by 230 V AC. Relay contacts tolerate compressor inrush currents up to a TV-5 surge rating of 80 A. They can also drive inductive motors rated at up to 3 FLA and 18 LRA, allowing the unit to start small evaporator fans or solenoids directly.

The six digital outputs handle defrost heaters, lights, and fan circuits with a resistive capacity of 8 A per pole. The control logic remains reliable down to a minimum relay load of 1 VA, allowing the outputs to operate low-power signaling devices. Field installation is simplified by DIN-rail mounting and a pluggable communication slot that accepts the AK-OB55 Lon option, enabling LonWorks networking for coordination among multiple refrigerated cases. The onboard real-time clock works with the available switches and input/output resources to run time-based defrost cycles without assistance from an external PLC. It also supports energy-saving night setbacks according to the programmed operating schedule.

Akv Output Current
0.5 A Max
Akv Power At 115 V Ac
1 x 20 W Max
Akv Power At 230 V Ac
2 x 20 W Max
Analog Inputs
6
Application Switches
9
Digital Inputs
3
Digital Outputs
6
Inrush Rating
TV-5 80 A
Lon Option Module
AK-OB55 Lon
Min Relay Load
1 VA
Mounting
DIN Rail
Relay Motor Load
3 FLA / 18 LRA
Relay Resistive Load
8 A

Frequently Asked Questions about 084B4057:

Q: What is the maximum AKV output current for the Danfoss 084B4057 controller?

A: The AK-CC55 controller can provide a maximum AKV output current of 0.5 A.

Q: How many analog inputs are available on the 084B4057 AK-CC55 case controller?

A: This controller supports up to 6 analog inputs for monitoring external sensors.

Q: How many application switches does the AK-CC55 controller have?

A: The 084B4057 model includes 9 application switches for user configuration purposes.

Q: What is the maximum relay resistive load supported by the Danfoss 084B4057?

A: A relay resistive load of up to 8 A can be handled by this device.

Q: How is the AK-CC55 084B4057 controller installed or mounted?

A: This controller mounts to a DIN rail for easy installation in control panels.