The Bosch Rexroth Indramat HNL01.1E-3400-S0202-A-480-NNNN is part of the HNL Mains Chokes series. This current-compensated mains choke is rated for a 3-phase AC supply voltage of 400 to 480 V with a frequency of 50 or 60 Hz. It features an IP10 degree of protection and a feeding supply system.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The HNL01.1E-3400-S0202-A-480-NNNN mains choke is produced by Bosch Rexroth Indramat and belongs to the HNL Mains Chokes series. Installed between the utility supply and an AC drive, it adds inductance that smooths phase current and reduces voltage ripple before power reaches the rectifier stage. By limiting steep current changes during switching events, the choke lowers harmonic distortion and reduces electrical stress on drives, cables, and upstream protective devices. This behavior is useful when several inverters accelerate from the same plant feeder, because input current remains more controlled across the shared line. It is commonly used in conveyor systems, machining centers, and assembly equipment where multiple drives operate from one incoming supply.
The electrical interface is rated at 3 × AC 400–480 V, -15/+10%, 50/60 Hz, so the unit can operate on common low-voltage industrial power systems without tap changes. Its enclosure has an IP10 degree of protection, which means the choke is intended for installation inside a ventilated control cabinet where accidental contact with live parts is limited. Because the protection level is low, the unit is not intended for exposed mounting on open machinery or in areas where direct contact is possible. The unit uses a current-compensated winding that helps reduce common-mode noise and keeps leakage flux low during operation. This arrangement is suited to input conditioning on a shared three-phase supply, especially where several drives can influence line quality.
The choke works as a feeding element, which means it conditions incoming power before it reaches the drive's DC link. Placed on the line side of the inverter, it helps moderate current peaks drawn by the rectifier and supports smoother input behavior in shared panels. The unit is identified as Design version 1 and Series 01. These codes indicate the product generation and help match the choke to compatible drive hardware without changing the basic operating role of the component.
Frequently Asked Questions about HNL01.1E-3400-S0202-A-480-NNNN:
Q: What mains connection voltage does the HNL01.1E-3400-S0202-A-480-NNNN support?
A: The HNL01.1E-3400-S0202-A-480-NNNN is designed for use with mains connection voltages between 400 and 480 V AC (three-phase), with a tolerance of -15% to +10% at 50/60 Hz.
Q: What is the degree of protection for the HNL01.1E-3400-S0202-A-480-NNNN?
A: This model features a degree of protection rated at IP10, meaning it is protected against accidental contact with enclosed moving parts.
Q: Does the HNL01.1E-3400-S0202-A-480-NNNN offer any additional current-compensating features?
A: The HNL01.1E-3400-S0202-A-480-NNNN includes a current-compensated design option for improved electromagnetic compatibility.
Q: Which design version is the HNL01.1E-3400-S0202-A-480-NNNN?
A: This choke is classified as a Design Version 1 model.
Q: What type of supply system is the HNL01.1E-3400-S0202-A-480-NNNN intended for?
A: The HNL01.1E-3400-S0202-A-480-NNNN is for use in feeding supply systems as indicated in its specifications.