FVCA01.1-90K0-3P4-MDA-LP-P002-01V01 Bosch Rexroth Indramat
MPN: R912004682
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The Bosch Rexroth Indramat FVCA01.1-90K0-3P4-MDA-LP-P002-01V01 is a frequency converter from the FVCA Frequency Converters series. It delivers an output power of 90 kW and operates with a nominal voltage of 400 V across three phases. The converter supports V/f, SVC, and FOC control technologies, includes a PID controller, and features ModBus communication and an LCD display.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The FVCA01.1-90K0-3P4-MDA-LP-P002-01V01 frequency converter is produced by Bosch Rexroth Indramat within the FVCA Frequency Converters series. The device conditions power from three-phase mains and supplies 0 to 400 Hz output for induction or synchronous machines used in automated lines. It communicates through Modbus and can be adjusted directly through a front-mounted potentiometer. V/f, SVC, and FOC control modes are supported, and an integrated PID regulator provides closed-loop speed or pressure control. Switching is handled at a 2.0 kHz carrier with an SVPWM method, and status and parameter values are shown on the LCD display. The unit is design revision 1 and version 01.
Electrically, the converter is rated for a nominal bus of 400 V and can draw 184 A from the supply to deliver a continuous output current of 176.0 A. Within the permitted range of 3 AC 380…480 V (-15%/+10%), the unit supplies up to 90.0 kW of mechanical power, while the apparent power at the feeder reaches 116.0 kVA. The incoming energy is rectified and raised to a DC link equal to the mains voltage multiplied by 1.41 before pulse-width modulation. The converter uses frame size G and is supplied with a factory-installed C3 EMC filter for industrial environments. It also accepts 50 Hz or 60 Hz grids, and the enclosure measures 450 mm in width, 302.5 mm in depth, and 700 mm in height.
Transient demands are handled through an overload margin of 200 % In for 1 s; 150 % In for 60 s, allowing short accelerations without drive shutdown. Thermal limits are set by an operating range of -10 to +40 °C, with permissible humidity below 90% RH, and the enclosure has an ingress rating of IP 20. Braking energy is dissipated through an external resistor because the internal brake chopper is prepared but not populated. The housing weighs 58.0 kg, and the unit is release 01 in Line 01.
Frequently Asked Questions about FVCA01.1-90K0-3P4-MDA-LP-P002-01V01:
Q: What is the nominal voltage required by the FVCA01.1-90K0-3P4-MDA-LP-P002-01V01 frequency converter?
A: The FVCA01.1-90K0-3P4-MDA-LP-P002-01V01 supports a nominal voltage of 400 V for operation.
Q: What is the output power rating of the FVCA01.1-90K0-3P4-MDA-LP-P002-01V01?
A: This frequency converter delivers an output power of 90.0 kW.
Q: What is the default PWM frequency for the FVCA01.1-90K0-3P4-MDA-LP-P002-01V01?
A: The default PWM frequency of this model is set to 2.0 kHz.
Q: Does the FVCA01.1-90K0-3P4-MDA-LP-P002-01V01 include an internal braking resistor?
A: An external braking resistor is required for braking resistance with this frequency converter.
Q: Which communication interface is available on the FVCA01.1-90K0-3P4-MDA-LP-P002-01V01?
A: The FVCA01.1-90K0-3P4-MDA-LP-P002-01V01 provides communication via the ModBus interface.