The Bosch Rexroth Indramat CDB01.1C-SE-ENS-ENS-ENS-ENS-NN-S-NN-FW is part of the CDB Control Units series and has a base power of 9 watts. It offers a digital output current of 500 mA and operates with an inrush current of 6 amps. The unit features an ENS converter width of 12 bits with a cutoff frequency of 500 kHz.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The CDB01.1C-SE-ENS-ENS-ENS-ENS-NN-S-NN-FW belongs to the CDB Control Units series manufactured by Bosch Rexroth Indramat. This plug-in control section is installed on IndraDrive power units to coordinate two servo axes, exchange diagnostic data, and interface with higher-level automation networks. Within a drive stack, it handles motion sequencing, digital I/O processing, and encoder evaluation so the drive can close velocity and position loops without an external PLC.
Power for the logic electronics is limited to 9 W, keeping internal dissipation low and reducing cabinet cooling load. Each digital output can source up to 500 mA, while the collective limit for a group of outputs is 1000 mA; these ratings limit how many valves or relays the board can drive directly. During power-up, the control section draws an inrush of 6 A, so upstream supplies must tolerate that brief surge. A maximum pulse width of 60 ms is allowed on fast inputs, permitting capture of short sensor edges without loss. The SERCOS III bus can be updated every 1000 µs to synchronize axis commands, and the integrated SE option card adds 2 W of additional load for safety functions. For service access, the RS-232 port transmits parameter data at up to 115 kBaud.
The ENS interface processes encoder sinusoidal signals with a 12-bit resolution after internal interpolation and maintains frequency response up to 500 kHz, supporting high-speed motors. Its input network presents 120 Ω termination and consumes 6 W, while a separate supply delivers 11.6 V at 500 mA to the sensor head. Group relay contacts on the baseboard are rated at DC 24 V / 1 A, enabling direct switching of brake coils or status lamps. The separate sensor supply and relay outputs support direct connection of feedback devices and external status circuits.
Frequently Asked Questions about CDB01.1C-SE-ENS-ENS-ENS-ENS-NN-S-NN-FW:
Q: What is the base power consumption for the CDB01.1C-SE-ENS-ENS-ENS-ENS-NN-S-NN-FW control unit?
A: The CDB01.1C-SE-ENS-ENS-ENS-ENS-NN-S-NN-FW has a base power consumption of 9 W.
Q: What is the maximum RS232 communication rate of the CDB01.1C-SE-ENS-ENS-ENS-ENS-NN-S-NN-FW?
A: It supports a maximum RS232 communication rate of 115 kBaud for serial connections.
Q: What is the maximum inrush current for the CDB01.1C-SE-ENS-ENS-ENS-ENS-NN-S-NN-FW?
A: This unit can handle a maximum inrush current of 6 A during power-up.
Q: What is the digital output group current of the CDB01.1C-SE-ENS-ENS-ENS-ENS-NN-S-NN-FW?
A: The digital output group current is rated at 1000 mA for this model.
Q: What is the minimum Sercos cycle supported by the CDB01.1C-SE-ENS-ENS-ENS-ENS-NN-S-NN-FW control unit?
A: The smallest supported Sercos cycle time is 1000 µs for this unit.