The EPP2038-0002 from Beckhoff, part of their EPP EtherCAT P Box Modules, supports the EtherCAT protocol and offers 8 outputs. It features a nominal output voltage of 24V DC, short-circuit proof channels with a max output current of 2A per channel. Weighing approximately 165 grams, it measures 30 x 126 x 26.5 mm.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The EPP2038-0002 EtherCAT P box module provided by Beckhoff encompasses digital outputs. This module operates using eight channels. The product is equipped with diagnostics capability. This device processes digital or binary signals. The units current rating for all its outputs is not more than 3 A. Its channels depend on LEDs to indicate their signal states. This module supports overloading for a short period.

The product connects signals in binary control format from an automation system to process-level actuators. This devices diagnostics offer assurance of reliable system availability. The units outputs are protected against short circuits. It can detect an open load or a wire that is broken for all channels. This module uses M12 connectors for signal connections. The products outputs process a maximum load current of 0.5 A. This device features 6 mA input current at 24 VDC. The unit can withstand 1000 shocks in three axes in each direction. Its outputs feature protection against polarity reversal.

This module has two red-colored protective caps on the EtherCAT P socket with an M8 connector. The product weighs close to 165 g. This device has IP 67 protection degree if the protective caps are properly seated in place. This devices EtherCAT slave master is loaded in the ESI-EEPROM for the related EtherCAT master. The unit is usable in dust, wet, and/or dirty environments because of its completely sealed housing. Its connectors are coded mechanically to avoid interchanging with the EtherCAT connectors. This EtherCAT P box module has two supply voltages.

Auxiliary Power Current
typ. 20 mA + load
Bus Interface
2 x M8 socket, P-coded, shielded
Current Consumption From Us
typ. 100 mA
Diagnostics
short-circuit, open load detection (min. load > 200 mA)
Dimensions (w X H X D)
30 mm x 126 mm x 26.5 mm
Load Type
ohmic, inductive, lamp load
Max. Output Current
2 A per channel, individually short-circuit proof, A^' 3 A
Nominal Output Voltage
24 V DC (-15%/+20%)
Number Of Outputs
8
Output Connections
M12 x 1, 5-pin, a-coded
Protocol
EtherCAT
Short-circuit Current
typ. 15 A
Switching Times
typ. TON: 200 Aus, typ. TOFF: 200 Aus
Weight
approx. 165 g

Frequently Asked Questions about EPP2038-0002:

Q: What is the switching time of the EPP2038-0002 module?

A: The switching time of the EPP2038-0002 module is 200 Aus.

Q: How is the output connection of the EPP2038-0002 module established?

A: The output connection of the EPP2038-0002 module is established using a 5-pin M12 connector.

Q: What is the electrical isolation voltage of the EPP2038-0002 module?

A: The electrical isolation voltage of the EPP2038-0002 module is 500 V.

Q: What diagnostics does the EPP2038-0002 module incorporate?

A: The EPP2038-0002 module incorporates open load and short circuit detection.

Q: What protocol does the EPP2038-0002 module support?

A: The EPP2038-0002 module supports EtherCAT protocol.