EL9410-0018 Beckhoff
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The Beckhoff EL9410-0018 is part of the EL EtherCAT Terminals series and features a 24 VDC input voltage along with one additional power contact. It supports a power contact current of 10 Amps and is designed for mounting on a 35 mm rail, with an IP20 protection class. The terminal meets EMC standard EN 61000-6-2 / EN 61000-6-4 and has a diagnosis interface using LED and process image.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The EL9410-0018 is a Beckhoff terminal module in the EL EtherCAT Terminals series. It is used in control cabinets to distribute 24 VDC supply power to adjacent I/O stations while simultaneously returning status data to the PLC. The module maintains a stable logic and load-voltage segment inside industrial automation lines, linking the upstream power source to downstream terminals through a dedicated power contact and sending diagnostic information over the EtherCAT bus.
The terminal accepts an input of 24 VDC and can forward up to 10 A on its power contact, allowing actuators or sensors on the same string to draw load current without separate wiring. The internal E-bus feed is limited to 2 A, so logic electronics stay protected from high-current transients. With a process image width of 2 bits, the controller receives clear on and off flags for operating and error states that originate from the LED and process-image diagnostic interface. When the supply falls below 17 V, the undervoltage threshold triggers one of those bits, enabling an immediate reaction in the control program. One additional power contact extends the 24 V distribution line, and the module makes no electrical use of the DIN rail, keeping grounding schemes predictable across the installation.
Compliance with EN 61000-6-2 / EN 61000-6-4 supports electromagnetic compatibility in industrial environments, and the housing carries a protection rating of IP20, so it is intended for shielded enclosures. Mechanical integrity is verified against shock per EN 60068-2-27 and vibration per EN 60068-2-6, supporting reliable operation on moving or stamping machinery. Occupying only 35 mm of rail width, the terminal leaves space for neighboring modules. Front-mounted LEDs duplicate the process image so power status can be checked without connecting diagnostic tools.
Frequently Asked Questions about EL9410-0018:
Q: What input voltage does the EL9410-0018 EtherCAT terminal require?
A: The Beckhoff EL9410-0018 operates with an input voltage of 24 VDC.
Q: What is the maximum current supported by the EL9410-0018 power contacts?
A: This terminal can handle a maximum power contact current of 10 A.
Q: How can system diagnostics be accessed on the EL9410-0018?
A: The device features both LED and process image diagnosis interfaces for status monitoring.
Q: What is the undervoltage threshold for the EL9410-0018?
A: The EL9410-0018 has an undervoltage threshold set at 17 V.
Q: Which EMC standards does the EL9410-0018 comply with?
A: This terminal meets EN 61000-6-2 and EN 61000-6-4 EMC standards.