The Beckhoff EL9227-6600, part of the EL EtherCAT Terminals series, features a nominal voltage of 24 V DC and weighs approximately 55 grams. It has two inputs, two outputs, and an adjustable advance warning output load ranging from 50–100%. The terminal includes reverse polarity switch-off.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The model EL9227-6600 processes as an EtherCAT Terminal to ensure reliable power circuit protection with adjustable control across two channels. Made by Beckhoff , the firm excels through the remarkable design of industrial automation parts.
The EL9227-6600 EtherCAT terminal operates as a two-channel overcurrent protection design for 24 V DC voltage systems. It holds reliable current input handling with a maximum input current capacity of 10 A. It provides a rated current adjustment feature that aids in allowing current settings between 1 A and 4 A in clear 1 A increments for flexible load adaptation. It is built within the module as a fail-safe element rated at 6 A (T) by ensuring circuit interruption at the specified limit for added safety during fault conditions. It also includes an advance warning function for low-voltage detection which can be configured between 17 V DC and 24 Volts DC. The reverse polarity switch-off process enhances its protective behavior by preventing problems when opposite switching is applied. Also, there are three adjustable steps for the reverse switch-off feature by permitting a custom defensive reaction according to system needs.
The EL9227-6600 EtherCAT terminal has two input channels and simple signal handling which can manage a high current load of 10 A via its power connections. The terminal helps with regulated system reset procedures by maintaining a hold duration of 10 seconds following an output switch-off event based on temperature conditions. Also, it has an output load warning that can be adjusted from 50% to 100% by giving early warnings before the capacity reaches its maximum. It contains an overvoltage power-off feature by activating at a DC level equal to or exceeding 32 V.
Frequently Asked Questions about EL9227-6600:
Q: How many channels are supported by the EL9227-6600 terminal for input and output?
A: The EL9227-6600 terminal features two inputs and two outputs, ensuring stable connection points for circuit monitoring and control.
Q: Does the EL9227-6600 terminal include a reverse polarity protection feature?
A: Yes, the EL9227-6600 terminal is equipped with reverse polarity switch-off to prevent damage from incorrect power supply connections.
Q: What is the rated current adjustment range of the EL9227-6600 terminal?
A: The rated current on the EL9227-6600 terminal is adjustable between 1 A and 4 A in precise 1 A steps.
Q: What integrated fail-safe element is available in the EL9227-6600 terminal?
A: The EL9227-6600 terminal includes a 6 A (T) fail-safe element for effective safety interruption in case of fault conditions.
Q: How does the EL9227-6600 terminal handle overvoltage situations?
A: The EL9227-6600 terminal features overvoltage power-off activation at 32 V DC or higher to protect connected circuits.