EL3446
Wake Industrial LLC is not an authorized distributor of this product.
MPN: EL3446-0000
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
-
In-Stock, Ships Fast
The EL3446 is a 4-channel energy measurement terminal manufactured by Beckhoff. As part of the EL EtherCAT Terminals series, it features a measuring range of 100V to 253V AC and supports direct current measurements up to 5A RMS. It is DIN rail-mountable with dimensions of 24mm x 100mm x 68mm.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The Beckhoff EL3446 is a 4-channel energy measurement terminal from the EtherCAT Terminals product line that is suitable for accurate and reliable energy consumption measurement. It has the capability to measure AC voltage within the range of 100 V to 253 V from phase to neutral and DC current from 1 mA to 5 A RMS. The device is also capable of withstanding a permanent current overload of 10 A. With the capability to measure voltage and current with 16-bit resolution and a 10 kHz sampling rate, the EL3446 provides high accuracy and dependable data transfer in industrial automation and energy systems. The terminal features EtherCAT as the data transfer port, and it allows installation on the DIN rail. It measures 24mm in width, 100mm in depth, and 68mm in height, which means that it can easily be installed in control cabinets since it occupies limited space.
The EL3446 is functional in an operating temperature that is between 0 degrees Celsius and 55 degrees Celsius. This means that it can operate in indoor environments where multiple electronic devices are used, like automation control panels or server rooms. This ensures that the device does not overheat or freeze, which can lead to some form of damage within the device. Ventilation and good temperature conditions must be maintained in the working climate so that the devices remain stable.
This energy measurement terminal is highly accurate with an accuracy of up to ~0.5%. This ensures that the device's energy consumption readings are highly accurate, enabling effective monitoring and improved energy efficiency. This helps industries track how much energy is being used, avoid energy wastage, and make better decisions to improve energy efficiency.
Frequently Asked Questions about EL3446:
Q: What is the number of channels for the EL3446-0000 terminal?
A: The EL3446-0000 terminal has 4 channels.
Q: What is the current overload rating for the EL3446-0000 terminal?
A: The current overload rating for the EL3446-0000 terminal is 10 A (permanent).
Q: What is the accuracy of energy measurement for the EL3446-0000 terminal?
A: The accuracy of energy measurement for the EL3446-0000 terminal is ~0.5% of the measured value.
Q: What is the power consumption for the EL3446-0000 terminal?
A: The power consumption for the EL3446-0000 terminal is typically 2.0 W.
Q: What is the operating temperature range for the EL3446-0000 terminal?
A: The operating temperature range for the EL3446-0000 terminal is 0 degrees C to +55 degrees C.