4.95 based on 202 reviews

🙶 Great service, they have the parts i needed in stock. 🙷

EL3174-0090 Beckhoff

In-Stock, Ships 3-5 Days

Preparing your secure checkout page...

The Beckhoff EL3174-0090 is part of the EL EtherCAT Terminals series and features four analog inputs with a SAR ADC type and 16-bit resolution. It has a common-mode voltage of 35 V, an input filter of 5 kHz, and supports a minimum EtherCAT cycle time of 200 microseconds. The terminal's dimensions are 15 x 100 x 70 millimeters and it provides overcurrent protection up to 50 mA.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The EL3174-0090 is an analog input terminal manufactured by Beckhoff for the EL EtherCAT Terminals series. It installs on a standard EtherCAT rail and converts field-level voltage or current signals into digital data that a controller can log or regulate. By offering isolated measurement channels and integrated conversion electronics, the terminal supports compact, high-speed data acquisition in distributed automation cells without separate analog boards.

This model provides 4 analog inputs that are sampled by a SAR converter in multiplex sequence, so each channel is read in turn. Users gain precise numeric values because the converter delivers 16 bit resolution, giving 65,536 quantization steps across the measurement span. A built-in 5 kHz input filter suppresses high-frequency noise before conversion, while the 107% extended range allows the module to detect slight overrange excursions without clipping. The common-mode voltage limit of 35 V protects the circuitry against potential differences between sensors, and the terminal uses differential voltage measurement and single-ended current measurement. Cycle times down to a 200 µs minimum EtherCAT cycle keep control loops fast, while <1 µs distributed clock precision aligns the terminal’s sampling points with system-wide timing.

Power for the bus interface is drawn from the EtherCAT backplane and amounts to 170 mA E-bus current, which helps when sizing the total segment supply. Each input path includes 50 mA overcurrent protection that disconnects the channel if a wiring fault creates excessive load. For current-mode measurements, the terminal uses an 85 Ω input resistance in current mode, which minimizes voltage drop through shunt sensing. In voltage mode, it presents >200 kΩ input resistance in voltage mode to avoid loading delicate sensor outputs. The enclosure measures 15 × 100 × 70 mm, so the narrow housing conserves cabinet space while preserving the terminal’s multiplex sampling behavior and SAR accuracy.

Adc Type
SAR
Analog Inputs
4
Common-mode Voltage
35 V
Current Input Resistance
85 Ω
Dimensions
15 x 100 x 70 mm
Distributed Clock Precision
<1 µs
E-bus Current
170 mA
Extended Range
107%
Ground Reference
U diff.; I single-ended
Input Filter
5 kHz
Min. Ethercat Cycle
200 µs
Overcurrent Protection
50 mA
Resolution
16 bit
Sampling Type
Multiplex
Voltage Input Resistance
>200 kΩ

Frequently Asked Questions about EL3174-0090:

Q: How many analog input channels are available on the EL3174-0090?

A: The EL3174-0090 terminal features four analog input channels for signal acquisition.

Q: What type of ADC does the EL3174-0090 utilize?

A: The analog-to-digital converter in the EL3174-0090 is of the SAR (Successive Approximation Register) type.

Q: What is the maximum common-mode voltage supported by the EL3174-0090?

A: This terminal supports a common-mode voltage up to 35 V for its inputs.

Q: What is the resolution of the analog inputs on the EL3174-0090?

A: The EL3174-0090 offers a 16-bit resolution for precise analog signal conversion.

Q: What is the minimum EtherCAT cycle time of the EL3174-0090?

A: The minimum supported EtherCAT cycle time for this terminal is 200 microseconds.


Internal Product Review

  • ‘‘The EL3174-0090 is a Beckhoff EL EtherCAT analog input terminal with 4 analog inputs and 16-bit resolution. SAR conversion and a 200 µs minimum EtherCAT cycle give the terminal fast, consistent signal acquisition for tightly timed control tasks. Distributed clock precision below 1 µs makes the EL3174-0090 a strong choice for synchronized measurement applications.’’