EL3062-0030 Beckhoff
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The Beckhoff EL3062-0030 is part of the EL EtherCAT Terminals series and features two analog inputs with a resolution of 12 bits and a conversion time of 0.625 milliseconds. It operates with a typical E-bus current of 130 mA, supports single-ended ground reference, and carries an IP20 protection rating.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
Beckhoff’s EL3062-0030 is an analog input terminal in the EL EtherCAT Terminals series. It snaps onto a DIN rail alongside other terminals and acquires low-level process signals for PLC evaluation. By converting field voltages into digital words and forwarding them over the EtherCAT backplane bus, it brings sensor feedback for pressure, temperature, or level into industrial automation systems that require compact, channel-dense I/O.
The terminal provides 2 analog inputs that share a single-ended ground reference, so connected transducers must reference the supply common. Each channel operates with a 0.625 ms conversion time, supporting responsive control loops. The converter has a 12-bit resolution, balancing precision and network bandwidth, while the module draws a typical 130 mA E-bus current from the internal power rail. The housing has an IP20 protection rating, making the terminal suitable for installation in an enclosed cabinet. The slice does not support the EtherCAT Distributed Clocks function. Applications requiring precise synchronization must therefore obtain timing from other compatible nodes in the system.
A front-end filter attenuates radio-frequency noise with a 1 kHz input filter cutoff, improving signal integrity before conversion. Field wiring has a dielectric strength of up to 40 V relative to the bus. Channel sequencing uses multiplexed sampling, which alternates acquisition between the two inputs during each cycle. Results are forwarded in a 16-bit output format that reserves four bits for status information. The installation position is variable, so the terminal can be mounted horizontally or vertically to suit the cabinet layout. The device has no local CoE storage, which means the controller retains its parameters instead of storing them within the terminal.