CX2500-M510 Beckhoff
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The Beckhoff CX2500-M510 is a fieldbus module from the CX Embedded PC Systems series that functions as a master for CANopen networks. It features a single 9-pin D-Sub connector and supports baud rates ranging from 10 kbaud to 1,000 kbaud. This module is designed to be mounted on the left side and allows a maximum of four modules per CPU.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The CX2500-M510 fieldbus module is supplied by Beckhoff for the CX Embedded PC Systems series. It plugs onto a CX CPU to give the controller a CANopen channel for exchanging process data with distributed devices. In an automation project it serves as the interface that translates internal tasks from the embedded PC into the serial CAN frames required for deterministic I/O updates. Adding this module lets an engineer implement high-speed motion sequences without dedicating separate PLC hardware.
The module assumes the bus role of Master, giving the PC authority to manage node boot-up, state changes, and synchronous PDO traffic. The physical connection is realized through a single D-Sub Connector with a pin count of 9; pin 7 carries CAN High, pin 2 routes CAN Low, and pins 3 and 6 provide ground reference. An integrated shield on pin 5 minimizes common-mode noise, while pins 1, 4, 8, and 9 remain unused for additional isolation. Communication speed is selectable from 10 kbaud up to 1,000 kbaud, enabling reliable signaling over both long and short cable runs. The transport layer complies with CANopen, allowing standardized object dictionary handling, heartbeat supervision, and emergency messaging in mixed-vendor systems.
The CX2500-M510 is classified as a fieldbus module and installs on the controller’s Left side, keeping the overall system width unchanged when several interfaces are added. Firmware in the embedded PC can enumerate up to 4 of these modules per CPU, so parallel CAN segments may operate with independent baud rates. Network wiring remains orderly because the design exposes only a single port, reflected in a connector count of 1. The specified shield pin, dedicated grounds, and reserved contacts work with the housing to maintain electromagnetic compatibility without external adapters.
Frequently Asked Questions about CX2500-M510:
Q: What bus role does the CX2500-M510 module provide in a CANopen network?
A: The CX2500-M510 fieldbus module operates as a CANopen Master, enabling the coordination and control of subordinate devices on the network.
Q: What is the maximum and minimum baud rate supported by the CX2500-M510?
A: This module supports communication speeds from 10 kbaud up to a maximum of 1,000 kbaud for CANopen connections.
Q: What type of connector is used on the CX2500-M510, and how many connectors are there?
A: The CX2500-M510 fieldbus module connects to the network using a 9-pin D-Sub connector and provides a single connector interface.
Q: How many CX2500-M510 modules can be installed per CPU?
A: Up to four of the CX2500-M510 modules can be added per CPU for flexible expansion.
Q: On which side of the CX Embedded PC system is the CX2500-M510 mounted?
A: The CX2500-M510 is designed to be mounted on the left side of the CX Embedded PC system.