The X20SA4430 features a sinc^3 input filter, overload detection via software, a test voltage of 500 VDC across the channel pair, and safety-related accuracy per channel (cat. 3) of 0.184 mA. Part of the X20 Series by B & R Automation, it includes configurable filter time between 1 and 66.7 ms.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
X20SA4430 is a safe analog input module. It is designed for the acquisition of current signals in safety-related applications. It works with X20 series terminal blocks with 16 pins. The module is equipped with two safe analog input pairs that can measure current ranging from 0.5 to 25 milliamps. Each of the input pairs has its own sensor power supply. These input channels support differential input. The output format is SAFEINT. The load is 230 to 420 Ohms for modules with hardware revision up to D3. The load is 185 to 245 Ohms for modules with hardware revision E0 or later. The input channels are protected against overcurrent and external voltages. The maximum permitted input signal is 30.5 Volts. An analog to digital converter (ADC) on the module supports 24-bit resolution.
The ADC uses sigma-delta conversion. The maximum conversion error is 0.3% at 0.5 to 4 milliamps and 0.08% for current between 4 to 25 milliamps. The input channels on the module are galvanically isolated. Input filter on the module is configurable. Nonlinearity of the X20SA4430 module is 0.003%. The hardware input filter on the module is a first-order low-pass filter with 500 Hertz cutoff. The software filter on the module is a Sinc3 filter. Resolution of the filter is 1 microamp per LSB. Overload detection on the X20SA4430 module is available via software. Test voltage for the channel bus is 500 Volts DC and for the channel pair to channel pair is 500 Volts DC. The filter time is configurable between 1 and 66.7 milliseconds. Nominal voltage for the sensor power supply is 29 Volts DC and the nominal output current is 60 milliamps (maximum).
Frequently Asked Questions about X20SA4430:
Q: What is the protection rating?
A: The protection rating is IP20.
Q: Which accessories are required for the module?
A: One safety-keyed terminal block and one safety-keyed bus module is required.
Q: What is the operating temperature for vertical mounting?
A: The operating temperature for vertical mounting is 0 to 50 degrees Celsius.
Q: What is the operating temperature for horizontal mounting?
A: The operating temperature for horizontal mounting is 0 to 60 degrees Celsius.
Q: Does the sensor power supply support short-circuit protection?
A: The sensor power supply supports short-circuit protection.