The 2AO300.6 analog output module is manufactured by B & R Automation and is part of the System 2010 Controllers series. It provides 16 bipolar voltage outputs with a resolution of 12 bits and an output signal of ±10 V. The module measures 285 x 40 x 185 mm, has a maximum power consumption of 10 W, and features a conversion time of 250 microseconds.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The 2AO300.6 is an analog output module manufactured by B & R Automation for the System 2010 Controllers series. It converts numeric setpoints generated by the CPU into stable bipolar voltages, allowing the controller to drive actuators, reference inputs, and other field devices that rely on a precise ±10 V command signal. By providing this digital-to-analog interface inside the same backplane, the module helps reduce wiring, simplifies cabinet layout, and keeps response latency low in industrial automation cells. This arrangement is useful when a control system must send smooth analog references to several devices without adding a separate external converter.
Inside the 40 mm wide housing, the module offers 16 bipolar voltage outputs, so one slice can support multiple axes or process loops. Each channel delivers a full-scale swing of ±10 V, compatible with standard drive and instrumentation inputs. A converter with 12 bit resolution divides that span into 4096 discrete steps, while a conversion time of 250 µs keeps new setpoints synchronized with fast machine cycles. At 20 °C, the deviation from ideal remains within ±0.25 %, which helps maintain predictable analog commands, and a first-order low-pass filter at 1000 Hz attenuates switching noise without sacrificing control bandwidth.
Accuracy stays within ±0.5 % across the broader 0 °C to 60 °C operating range, maintaining loop stability as cabinet temperature drifts. Each output can source or sink up to ±10 mA into loads of at least 1 kΩ, and fault current is limited to ±15 mA to protect the driver stage during short circuits. Overall demand remains below 10 W max, easing power-rail sizing when the module is mounted on BP200, BP201, or BP210 base plates. RPS isolation separates system power from field wiring, while the lack of per-channel isolation keeps the footprint compact for dense rack installations.
Frequently Asked Questions about 2AO300.6:
Q: How many outputs are available on the 2AO300.6 module and what is their voltage range?
A: This module provides 16 bipolar voltage outputs, each capable of ±10 V output.
Q: What is the maximum load allowed per output on the 2AO300.6?
A: The 2AO300.6 supports a maximum load per output of ±10 mA at loads of 1 kΩ or higher.
Q: What type of output filtering does the 2AO300.6 module use?
A: The 2AO300.6 outputs feature a 1st-order low-pass filter with a cutoff at 1000 Hz.
Q: Does the 2AO300.6 offer channel isolation on its outputs?
A: No channel-to-channel isolation is provided for the outputs on this module.
Q: What is the conversion time for the 2AO300.6 output signals?
A: This analog output module operates at a conversion time of 250 microseconds.