8AC140.60-2 B & R Automation
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The B & R Automation 8AC140.60-2 belongs to the 8AC Powerlink Modules series. It features a processor clock of 100 MHz, 16 MB DRAM, and 32 kB SRAM. The module offers 12-bit analog resolution, 20 megaohm analog input impedance, three digital I/O channels, and supports a maximum digital output current of 500 mA.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The 8AC140.60-2 belongs to the 8AC Powerlink Modules series manufactured by B & R Automation. This module is installed in distributed control cabinets to act as a communication and signal-conditioning node for industrial automation equipment. It bridges high-speed POWERLINK networking with local analog and digital inputs so that motion controllers or PLCs can sample field signals and drive actuators without requiring separate hardware tiers.
The local signal path uses an analog bandwidth of 10 kHz, and the internal filter passes fast transducer changes while suppressing higher-frequency noise. Sensors connect through an input stage whose impedance is 20 MΩ, and the high resistance minimizes loading errors on passive sources. Each converted value is delivered with 12-bit resolution, providing 4096 discrete steps across the ±10 V rated analog input range. A 32-kB SRAM cache buffers real-time variables, while 16 MB of DRAM stores protocol stacks and user code that run on a 100 MHz processor clock. System overhead is kept low, and the total power drawn from the backplane does not exceed 4.5 W, allowing dense panel mounting without oversized power supplies.
For fieldbus expansion, the CAN interface maintains reliable traffic over 1000 m of trunk line at rates up to 500 kbit/s, supporting remote drives or sensor clusters on large machines. PROFIBUS connectivity reaches 12 Mbit/s when higher deterministic throughput is required, and a diagnostic RS-232 port communicates at up to 115.2 kBaud for service access. Three digital I/O points share a combined output limit of 500 mA at the rated 24 VDC input level, and an event counter with 32-bit depth timestamps edge changes for sequence monitoring. Control logic persists in nonvolatile program memory, while buffered real-time variables remain available between bus cycles for synchronized motion and safety routines across the plant network.
Frequently Asked Questions about 8AC140.60-2:
Q: How many digital I/O channels are available on the 8AC140.60-2 module?
A: The 8AC140.60-2 supports up to three digital I/O channels for basic control and monitoring functions.
Q: What is the analog resolution of the 8AC140.60-2 Powerlink module?
A: This module offers a 12-bit analog resolution for precise measurement of analog signals.
Q: What digital input voltage does the 8AC140.60-2 accept?
A: The rated digital input voltage for this module is 24 VDC.
Q: What is the maximum supported CAN bus distance on the 8AC140.60-2?
A: The CAN interface on this module allows a maximum distance of 1000 meters.
Q: What is the processor clock speed on the B & R Automation 8AC140.60-2 module?
A: This module features a processor clock speed of 100 MHz, enabling efficient handling of tasks.