E11A302U002 Sanyo Denki
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The Sanyo Denki E11A302U002 is part of the SANUPS Power Supplies series and provides an input and output voltage of 208 V with a rated active power of 2.1 kW. It features 6 valve-regulated lead-acid batteries and offers 5 minutes of backup time. This power supply has a mass of 39 kg, a depth of 750 mm, and includes 4 IEC 60320-C13 and 3 IEC 60320-C19 output receptacles.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The E11A302U002 is a rack-mounted uninterruptible power supply assembled by Sanyo Denki for the SANUPS Power Supplies series. In automated production lines, it keeps PLCs, machine controllers, and network switches energized when utility power fails, allowing controlled shutdown or uninterrupted operation until generator power becomes available. The unit conditions incoming utility power, stores energy in an internal battery string, and delivers regulated 208-volt output to connected equipment. This power continuity helps motion sequences, data logging processes, and safety circuits remain active during short outages.
The utility input operates at 208 V, which is compatible with common North American industrial distribution systems. The rectifier, charger, and inverter have an input capacity of 2.7 kVA, allowing the UPS to process the required line current while accommodating harmonic distortion. On the load side, the unit supports up to 2.1 kW of active power and an apparent output of 3 kVA. These power limits determine the combined amount of connected equipment that the UPS can support without an overload. Coordination with upstream protection devices is simplified by a factory-installed breaker with a 15 A trip rating, so the supply circuit can be selected accordingly.
Energy storage is provided by six valve-regulated lead-acid batteries that supply approximately five minutes of backup time at the rated load. This interval allows active processes to stop safely, essential data to be saved, or standby generation to start. The detachable line cord terminates in a NEMA L6-20P plug, while downstream equipment connects through four IEC 60320-C13 receptacles and three C19 receptacles. During double-conversion operation, the electronics release up to 460 W of heat, so adequate airflow must be maintained around the 86 mm-high and 350 mm-wide chassis. The enclosure weighs 39 kg, requiring rack hardware that can support its installed mass. Its chassis extends 750 mm into the rack, which must be considered when selecting slide rails, support brackets, and an enclosure with sufficient depth.