14.F0.R33-3429
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
-
Available
The 14.F0.R33-3429 voltage modulator is CE Certified, air-cooled, features three-phase operation, and has an IP20 protection level. As part of the F0 Combivert Control Cabinet Series by KEB, it is mounted and employs a built-in PLC control system with a frequency range of 50/60Hz.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
14.F0.R33-3429 is a feature-rich frequency inverter. It is part of the F0 series from KEB Automation. The unit is designed for control of AC motors. The input voltage range is 380 to 480 Volts AC (three-phase, 50/60 Hertz). Power output of the unit is 11 kVA. The output voltage ranges from 0 to the input voltage. Rated output current of the 14.F0.R33-3429 inverter is 16.5 Amps. It can be used with 2/4 pole AC motors having 7.5 kilowatts rating. F0 series inverters support forced air cooling: cool air enters via an inlet located near the bottom of the unit and warm air is forced out via an outlet located near the top of the unit. The ambient temperature should remain within -10 to 45 degrees Celsius.
The 14.F0.R33-3429 unit is designed for rack mounting. It works at maximum 4 kilohertz switching frequency. The maximum mains fuse rating is 25 Amps. Overload capacity of the inverter is 111 to 130% for 5 minutes, 131 to 150% for 2 minutes, and 151 to 200% for 30 seconds. The power wire cross section recommended by KEB is 4 mm2. The specified power dissipation is 215 Watts at 4 kilohertz. Spacing requirements for the mounted inverter are 100 millimeters on the bottom and top, 50 millimeters on the sides and 50 millimeters on the front. These spacing requirements ensure smooth air circulation, which is critical for ensuring that the ambient temperature remains within specified limits. Site elevations above 3000 meters lead to output power derating at the rate of 1% per each additional 100 meters. If a mains fuse requires replacement, operators must wait for 1 minute after power disconnection and then proceed with the replacement.
Frequently Asked Questions about 14.F0.R33-3429:
Q: What is the rated power output?
A: The rated power output is 11 kVA.
Q: What is the voltage class of the inverter?
A: Voltage class of the inverter is 400 Volts.
Q: What is the rated output current?
A: The rated output current is 16.5 Amps.
Q: What is the maximum switching frequency?
A: The maximum switching frequency is 4 kHz.
Q: What is the recommended wire cross section?
A: The recommended wire cross section is 4 mm2.