29.DR.B28-5331 KEB
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The KEB 29.DR.B28-5331 is a three-phase input choke from the DR Motor Input Chokes series, featuring an inductance of 0.051 millihenry and an input voltage of 400 volts AC. It supports a rated current of 580 amps, a power loss of 470 watts, and weighs 73.5 kilograms with dimensions of 480 mm width, 390 mm height, and 210 mm depth.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
KEB manufactures the 29.DR.B28-5331 as part of its DR Motor Input Chokes series. The unit is a three-phase line reactor that installs between the mains supply and a motor drive to limit inrush current, attenuate harmonics, and improve the drive’s resistance to network disturbances in automated machinery. By adding impedance to the supply path, the choke helps keep current ripple within acceptable levels and protects rectifier stages during grid transients. Its three-phase design also helps maintain balanced electrical behavior across the incoming supply lines.
The choke is designed for a supply of 400 V AC, and its core and winding geometry support a continuous current of 580 A without saturation. An inductance of 0.051 mH provides the impedance needed to filter the 50/60 Hz supply and higher-order components produced by pulse-width-modulated drives. The three-phase construction keeps voltage drops balanced across all lines. A short-circuit voltage of 4% indicates the expected terminal voltage reduction when rated current flows and helps with the selection of compatible upstream protection. Internal copper and iron losses total 470 W, so the enclosure must provide adequate ventilation to keep the windings within their permitted temperature range.
The laminated core measures 480 mm in width and 210 mm in depth, while the overall height reaches 390 mm with the terminal covers installed. These dimensions should be considered when selecting the mounting location and determining the required clearances for wiring and airflow. Four oblong mounting slots measuring 12 × 20 mm allow the choke to be bolted directly to a panel plate or machine frame without additional brackets. The unit weighs 73.5 kg, so suitable lifting equipment should be used during installation. A flat, rigid mounting surface helps support the reactor evenly and limits movement caused by vibration during operation.