Internal Product Review

The 00.C6.CC1-0400 is a KEB C6 Combicontrol bus coupler with 16 single-ended or 8 differential analog inputs for EtherCAT 100 Mbit/s systems. The 13-bit resolution and typical measuring error below ±0.4% support clean, dependable signal acquisition in control applications. Fast 580 µs conversion time makes the bus coupler a strong choice for responsive analog acquisition.

Sell Part
Have a part to sell?
Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The 00.C6.CC1-0400 is an analog I/O slice produced by KEB within the C6 Combicontrol Bus Couplers series. Integrated into EtherCAT-based machine networks, the module digitizes voltage signals from sensors or actuators and forwards the data to the central controller through the backplane E-bus. By translating field-level analog measurements into protocol-compatible process data, it supports closed-loop tasks such as temperature, pressure, or position regulation in industrial automation cells.

It accepts 16 single-ended channels or 8 differential channels, allowing a choice between space-saving common-ground wiring and higher-accuracy paired measurement. Each channel provides 13-bit resolution, so the 10 V span is subdivided into 8,192 counts, enabling a step size near 1.22 mV. The successive-approximation converter completes a scan of all inputs in 580 µs, keeping control loops responsive. An internal analog front end uses a typical 1 kHz filter, which attenuates higher-frequency noise before conversion. Power for the A/D stages is drawn from the backplane, and the slice draws 220 mA from the E-bus for operation. Typical total measurement error remains below ±0.4%, and the supported voltage range covers both 0–10 V and ±10 V signals through a 36-pole spring-loaded terminal.

The communication side features a 100 Mbit/s EtherCAT interface, allowing the slice to occupy a deterministic, time-synchronized position on high-speed control networks. Signal loading on source devices is minimal because the input stage presents a resistance of greater than 1 MΩ, so most transducers operate without additional buffering. The module is rated for continuous operation from 0 to +55 °C, and it can be stored at temperatures as low as −25 °C. A molded housing with IP20 protection fits standard DIN rails and is paired with a 10-pole side system plug that carries both data and internal power distribution. This arrangement permits multiple analog slices to be stacked while maintaining compact wiring and deterministic bus timing.

Analog Inputs
16 Single-Ended / 8 Differential
Conversion Time
580 µs
E-bus Connector
10-Pole Side System Plug
E-bus load
220 mA
Fieldbus
EtherCAT 100 Mbit/s
I/o Connector
36-Pole Spring-Loaded Terminal
Input Filter
1 kHz (Typ.)
Input Resistance
>1 MΩ
Measuring Error
<±0.4 % (Typ.)
Operating Temp
0 to +55 °C
Power Supply
Via EtherCAT Coupler E-Bus
Protection
IP20
Resolution
13 Bit
Storage Temp
-25 to +70 °C
Voltage range
0…10 V; ±10 V

Frequently Asked Questions about 00.C6.CC1-0400:

Q: How many analog inputs does the KEB 00.C6.CC1-0400 support?

A: The 00.C6.CC1-0400 provides 16 single-ended or 8 differential analog inputs.

Q: What is the analog signal conversion time of the 00.C6.CC1-0400?

A: This model achieves a conversion time of 580 microseconds for input signals.

Q: What fieldbus protocol does the 00.C6.CC1-0400 use for communication?

A: The 00.C6.CC1-0400 operates on the EtherCAT fieldbus at 100 Mbit/s.

Q: What voltage range can the analog inputs on the 00.C6.CC1-0400 handle?

A: The voltage input range for this bus coupler is 0 to 10 V or ±10 V.

Q: What is the analog input resolution of the 00.C6.CC1-0400 bus coupler?

A: The rated resolution for analog input is 13 bits for this device.