FC-102P5K5T4P55H1UGXXXXSXXXXAXB2CXXXXDX
Wake Industrial LLC is not an authorized distributor of this product.
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The FC-102P5K5T4P55H1UGXXXXSXXXXAXB2CXXXXDX controller module has an input voltage range of 100-240 VAC, features 2 CAN interfaces, and provides electrical isolation. Part of the VLT FC 102 HVAC Drives series by Danfoss, it offers network capability and requires a screw-in mounting style with the TB712 terminal block.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The FC-102P5K5T4P55H1UGXXXXSXXXXAXB2CXXXXDX frequency converter is manufactured by highly trained engineers of the Internationally reputable Danfoss Automation. The converter comes with a user-friendly display unit through which qualified operators can interact with it in real-time. The typical shaft output of motors connected to this frequency converter is about 5.5 kilowatts; the converter also operates at a mains voltage that is between 380 to 480 volts. This converter is able to automatically detect alarm conditions and issue a warning to alert operators quickly enough to protect the converter. Examples of situations that can cause a warning to be issued include low voltage, DC under voltage, Low link voltage, high link voltage, and Main Phase Loss. The FC-102P5K5T4P55H1UGXXXXSXXXXAXB2CXXXXDX frequency converter operates with a continuous input current of 13 amperes, also the intermittent current for the converter is about 14.3 amperes.
The FC-102P5K5T4P55H1UGXXXXSXXXXAXB2CXXXXDX frequency converter is estimated to lose about 187 watts of power at the maximum permissible load; however, it is still able to manage an operation efficiency of about 0.97 under normal operating conditions. The recommended relative humidity supported for this converter is between 5 to about 93 per cent, and the maximum permissible ambient temperature for the operation of this frequency converter is about 50 degrees Celsius. The 24-hour average maximum ambient temperature is 45 degrees Celsius. The minimum ambient temperature during full-scale scale operation is 0 degrees Celsius; at reduced performance, the minimum ambient temperature at reduced performance is -10 degrees Celsius. During the transportation and storage of this product, ambient temperature should be between -25 to +65/70 degrees Celsius.
To avoid derating, the maximum installation height permissible for the FC-102P5K5T4P55H1UGXXXXSXXXXAXB2CXXXXDX frequency converter is about 1000 meters above sea level. There are about 4 programmable digital inputs on the converter. The input resistance of this input is approximately 4 kilo-Ohms.
Frequently Asked Questions about FC-102P5K5T4P55H1UGXXXXSXXXXAXB2CXXXXDX:
Q: What is the peak ambient temperature for this converter during operation?
A: The FC-202P1K5T2134F6393 frequency converter is able to withstand up to 50 degrees of ambient temperature.
Q: Does the FC-202P1K5T2134F6393 require a control cabinet?
A: Yes. The FC-202P1K5T2134F6393 is an IP20 protection product. It requires installation into a control cabinet for optimum protection.
Q: How often should operators carry out maintenance operation on this product?
A: This converter can operate for more than 10 years before any type of maintenance if required.
Q: Is the FC-202P1K5T2134F6393 frequency converter suited for operation in residential areas?
A: It is possible to use the FC-202P1K5T2134F6393 converter in residential and commercial environment.
Q: How does height affect the operation of the FC-202P1K5T2134F6393 frequency converter?
A: The FC-202P1K5T2134F6393 should not be installed above 1000 meters to avoid derating.