The Danfoss FC-102P18KT4E55H1XGXXOXSXXXXAXBXCXXXXDX is a 25 HP drive from the VLT FC 102 HVAC Drives series, offering a power rating of 18.5 kW. It operates with three phase power at 380 to 480 VAC and has a protection level of IP55 (Type 12). The drive includes a graphical local control panel and features an RFI filter rated at Class A1/B.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The FC-102P18KT4E55H1XGXXOXSXXXXAXBXCXXXXDX drive is manufactured by Danfoss and belongs to the VLT FC 102 HVAC Drives series. It is an AC variable-frequency drive intended for building automation, where it regulates the speed of induction motors in air-handling units, pumps, and chillers. Adjusting motor speed to match real-time demand can reduce unnecessary energy consumption during periods of partial load. The model connects directly to facility power distribution and supports indoor installation in mechanical rooms, plant areas, and industrial service corridors.
The power stage is rated at 18.5 kW, which is equivalent to 25 HP, allowing the inverter to operate medium-sized blower and circulation motors. It accepts an input range of 380–480 VAC from three-phase power, making it suitable for common 400 V class electrical networks. The enclosure has an IP55 / Type 12 rating that protects internal components against dust, dripping water, and low-pressure water jets. This protection allows the drive to be installed in many indoor plant locations without an additional protective cabinet. The drive does not include a brake chopper, making it appropriate for HVAC loads that do not require frequent regenerative braking.
Electromagnetic compatibility is supported by the built-in RFI Class A1/B (C1) filter, which limits conducted interference on the mains without requiring an external filter module. Parameter entry and local diagnostics are handled through the detachable graphical local control panel, which displays operating values, settings, warnings, and alarm history in plain text. The standard language pack makes the interface accessible for routine configuration and system monitoring. HVAC functions include flow compensation, which can adjust operation in response to changing system conditions. The printed circuit boards are not conformally coated, so the enclosure should remain properly closed to protect the internal electronics from moisture and airborne contaminants.
Frequently Asked Questions about FC-102P18KT4E55H1XGXXOXSXXXXAXBXCXXXXDX:
Q: What is the power rating and horsepower of the FC-102P18KT4E55H1XGXXOXSXXXXAXBXCXXXXDX VLT HVAC Drive?
A: This drive delivers a power rating of 18.5 KW, supporting applications up to 25 HP.
Q: What mains voltage is supported by the FC-102P18KT4E55H1XGXXOXSXXXXAXBXCXXXXDX?
A: The FC-102P18KT4E55H1XGXXOXSXXXXAXBXCXXXXDX operates on a mains voltage range of 380 to 480 VAC.
Q: What power phase configuration does the FC-102P18KT4E55H1XGXXOXSXXXXAXBXCXXXXDX require?
A: It is designed for use with three phase power supplies.
Q: What is the protection rating of the Danfoss FC-102P18KT4E55H1XGXXOXSXXXXAXBXCXXXXDX drive?
A: This model features an IP55 / Type 12 protection level, making it suitable for dusty and damp environments.
Q: What type of local control panel is featured on the FC-102P18KT4E55H1XGXXOXSXXXXAXBXCXXXXDX?
A: The drive includes a graphical local control panel (LCP) for easy on-site operation.