4.95 based on 202 reviews

🙶 I have always received exceptional service and support in my many years of working with Wake Industrial. 🙷

FC-102P Danfoss

In-Stock, Ships 3-5 Days

Preparing your secure checkout page...

The Danfoss FC-102P is part of the VLT FC 102 HVAC Drives series. It features 2 analog inputs with 10 bit resolution, 1 analog output at 12 bit resolution, and supports 2 digital outputs with a maximum current of 40 mA. The drive operates at a supply frequency of 50 or 60 Hz and includes 2 relay outputs of Form C type.

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The FC-102P is an AC variable frequency drive manufactured by Danfoss for the VLT FC 102 HVAC Drives series. It regulates fan and pump motors in building automation systems. By converting three-phase mains power into variable-voltage and variable-frequency output, the drive enables precise control of airflow, water circulation, and pressure while reducing energy consumption. Common HVAC control configurations allow integration with sensors, dampers, and supervisory controllers through built-in analog, digital, and relay interfaces. These interfaces support direct connections to common field devices without requiring separate signal-conversion modules.

The control stage provides a reference supply of 10.5 V ±0.5 V for potentiometer feedback and a 24 V auxiliary rail rated at 200 mA for externally powered transducers. Two analog inputs measure process signals with 0.5% full-scale accuracy and use 10-bit resolution for signal conversion. One analog output sends setpoints to valves or meters with 12-bit resolution. A pair of digital outputs and two Form C relay contacts forward operating status to building management systems. The 24 V source maintains regulation within a range of 24 V +1/-3 V to provide stable power for connected sensors. This combination of input and output channels supports pressure, temperature, flow, and equipment-status signals used in HVAC applications.

On the power side, the drive achieves a displacement power factor of >0.98, reducing reactive current demand on the supply equipment. For mechanical loads that experience short demand spikes, the inverter can sustain an overload of 110% for 60 s before derating. Control terminals accept up to 28 V DC on the digital inputs, providing a suitable operating range for standard control signals. Each transistor digital output can deliver 40 mA to operate external indicators or compatible interface devices. The inverter is preset for 50/60 Hz utility grids, allowing operation with the common supply frequencies used in commercial and industrial facilities. Its transistor outputs operate alongside the relay contacts to provide separate signaling paths for run status, alarms, or other control functions.

10 V Output Voltage
10.5 V ±0.5 V
24 V Output Max Load
200 mA
24 V Output Voltage
24 V +1/-3 V
Analog Input Accuracy
0.5% FS
Analog Input Resolution
10 bit (+ sign)
Analog Inputs
2
Analog Output Resolution
12 bit
Analog Outputs
1
Digital Input Max Voltage
28 V DC
Digital Output Max Current
40 mA
Digital Outputs
2
Displacement Power Factor
>0.98
Overload Torque
110% for 60 s
Product Group
VLT HVAC Drive
Relay Output Type
Form C
Relay Outputs
2
Series Identifier
102
Supply Frequency
50/60 Hz

Frequently Asked Questions about FC-102P:

Q: How many analog inputs are available on the FC-102P drive?

A: The Danfoss FC-102P provides two analog inputs for process signals.

Q: What is the analog output resolution on the Danfoss FC-102P?

A: The analog output resolution of the FC-102P is 12 bits, allowing fine gradation of signal values.

Q: What is the displacement power factor of the FC-102P?

A: The displacement power factor for the FC-102P exceeds 0.98, supporting efficient energy usage.

Q: What is the maximum current available from the digital outputs on the FC-102P?

A: The FC-102P model can supply a maximum digital output current of 40 mA.

Q: How much overload torque can the FC-102P withstand and for how long?

A: This model supports overload torque up to 110% for 60 seconds.


Internal Product Review

  • ‘‘The FC-102P is a Danfoss VLT HVAC drive suited for building automation service, with 50/60 Hz supply frequency and a displacement power factor above 0.98. Control performance is impressive, supported by 0.5% FS analog input accuracy and 110% overload torque for 60 s. A strong choice for HVAC applications requiring efficient and dependable drive operation.’’