The 131G1430 HVAC drive offers a power rating of 37 kW / 50 HP, supports three-phase input voltage ranging from 525 to 600 VAC, and features an enclosure rating of IP21 / Type 1. As part of the VLT FC 102 HVAC Drives by Danfoss, it delivers a continuous current of 54 A and has a net weight of 36.89 kg.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
The 131G1430 represents the VLT FC 102 HVAC Drive manufactured by Danfoss. The company is known for delivering reliable drive solutions for HVAC applications. This drive is part of the 102 series and is built to ensure efficient motor control in demanding environments. It is engineered for dependable performance while maintaining system stability in different operating conditions.
The 131G1430 VLT FC 102 HVAC Drive supports a power rating of 50 HP. It operates with a three-phase configuration and handles a main voltage range of 525 to 600 VAC. The drive is constructed with protection class IP21 which ensures safety against solid objects and limited moisture. It features a graphical LCP control panel for precise monitoring and easy parameter configuration. The installed software comes with a standard language pack to meet diverse usage needs. The drive is designed in frame size C1 with a net weight of 36.89 kg. It has a mounting plate width of 308 mm and a distance of 272 mm between mounting holes. To ensure effective thermal management the cooling clearance requirement is 200 mm. The unit can operate reliably at a maximum ambient temperature of 55 °C. It supports installation up to 1000 m above sea level without performance loss. For protection, the drive is compatible with a recommended maximum fuse gG-160 and a maximum trip level of 160 A. The ordering code for FC-102P37KT6E21HXXGXXXXSXXXXAXBXCXXXXDX is 131G1430.
The 131G1430 VLT FC 102 HVAC Drive supports the recommended circuit breaker NZMB2-A200 for electrical safety. The product meets EMC standards EN 61800-3 for emission compliance. It is rated under energy efficiency class IE2 which confirms optimized performance. The drive accepts a main cable cross-section of 50 mm^2 which supports stable connectivity and secure installation.
Frequently Asked Questions about 131G1430:
Q: How does the graphical LCP panel improve drive usability in 131G1430 drive?
A: The graphical LCP panel enhances precision monitoring by displaying key parameters clearly. It simplifies parameter adjustment, ensuring accurate system setup in HVAC operations.
Q: How does the recommended fuse gG-160 protect the drive?
A: The fuse provides overload protection during electrical surges. It ensures the 131G1430 drive operates safely under high inrush current conditions.
Q: Why is cooling clearance of 200 mm critical in 131G1430 drive?
A: The clearance ensures proper airflow around the drive. It prevents overheating and maintains stable performance at high ambient temperatures.
Q: How does EMC compliance EN 61800-3 benefit the 131G1430 drive?
A: The compliance reduces electromagnetic interference during operation. It ensures the drive can operate in sensitive environments without disrupting nearby electronic systems.
Q: Why is trip level setting of 160 A significant in 131G1430 drive?
A: The trip level protects against overcurrent damage. It ensures secure drive operation under high electrical load scenarios.