131F5454
Wake Industrial LLC is not an authorized distributor of this product.
MPN: FC-102P30KT4E20H2XGXXXXSXXXXAXBXCXXXXDX
No Tariffs On US Orders- Straightforward Pricing: No Rush Fees, No Credit Card Fees
The 131F5454 is a three-phase HVAC drive rated at 30 kW / 40 HP with an output current of 61 A. Manufactured by Danfoss, it is part of the VLT FC 102 HVAC Drives series and features an IP20 enclosure rating. It includes a graphical LCP, weighs 27 kilograms, and measures 242mm wide, 650mm tall, and 260mm deep.
To contact sales for pricing and lead time:
Payment Methods
Shipping Methods
Our Credentials
Product Description:
131F5454 is a drive that is developed especially for HVAC applications (heating, refrigeration, and ventilation). The VLT 102 series includes standalone drives that can be mounted outside cabinets and enclosed drives designed for fast installation. 131F5454 is a 30 kilowatts drive designed for use on AC mains where the supply voltage ranges from 380 to 480 Volts AC. Its IP20 chassis does not protect fully from dust or water, and therefore mandates installation inside a cabinet. A graphical control panel is available on the front panel. It includes a large display and keypad for easy operator input and configuration. Danfoss supplies the drive with the latest software version. Frame size of the drive is B4. The drive has a modular design with four slots for optional feature cards. All four slots on this drive are unoccupied.
Operators can install options cards in these slots if and when a specified need arises. The only permitted mounting orientation is vertical. Weight of the drive is 19 kilograms and its volume is 105.7 liters. Height, depth, and width of the drive are 516 millimeters, 242 millimeters, and 229 millimeters respectively. When operating under optimal ambient conditions the power output of the 131F5454 drive is 42.3 kVA and the power loss at maximum load is 698 Watts. As per the documentation, the maximum allowed ambient temperature is 50 ⁰C and the 24-hour average peak temperature should not exceed 45 ⁰C. Higher temperatures cause a reduction in the drive’s performance. Danfoss has designed the drive with high-quality components and its rated efficiency is 0.98. For trouble-free installation and operation, only skilled and trained personnel should handle the AC drive.
Frequently Asked Questions about 131F5454:
Q: What is the vibration test rating?
A: The vibration test rating is 1.0 g.
Q: What is the maximum ambient temperature?
A: The maximum ambient temperature for full output is 50 ⁰C.
Q: What is the maximum input current?
A: The maximum input current is 55 Amps.
Q: What is the efficiency of the drive?
A: Efficiency of the drive is 0.98.
Q: What is the power loss at max load?
A: The power loss at max load is 698 Watts.