The Danfoss 131B4268 is part of the VLT FC 102 HVAC Drives series and is designed for three phase power at 380 to 480 VAC. It features a power rating of 30 kW (40 HP), an IP55 protection level, and includes a graphical local control panel. The drive comes with a standard language pack and an RFI filter of Class A1/B (C1).

Warranty
Wake Industrial Warranty

Quote Request Form:

To contact sales for pricing and lead time:

Payment Methods

Visa
Mastercard
AmEx
Wire Transfer

Shipping Methods

DHL
UPS
FedEx
Freight

Our Credentials

Cary Chamber
DUNS Registered
SAM Registered
BBB Accredited

Product Description:

The 131B4268 is a variable frequency drive produced by Danfoss for the VLT FC 102 HVAC Drives series. The unit regulates the speed of fan, pump, and compressor motors used in building automation systems, ventilation equipment, and hydronic circuits. It adjusts motor output in response to pressure, temperature, or flow demands, which can reduce unnecessary energy use while maintaining stable operation. Its control functions also support gradual acceleration and deceleration, reducing mechanical stress on connected equipment and limiting abrupt changes in airflow or fluid pressure.

The drive delivers up to 30 kW, which corresponds to 40 HP. It accepts an input voltage range of 380 to 480 VAC from a three-phase power supply, allowing connection to common industrial electrical systems. The IP55 / Type 12 enclosure protects internal components against dust, incidental contact, and water jets. The unit does not include a brake chopper, so applications that require dynamic braking must use suitable external equipment. Its mains section is supplied without a factory disconnect, allowing the required isolation equipment to be selected for the installation. The safe-stop input provides basic terminal isolation, while the standard language pack supplies the default interface languages for operation and setup.

Conducted emission control is provided by an integrated RFI Class A1/B (C1) filter, which reduces high-frequency electrical noise without requiring a separate C1 filter card. Operating data, parameter menus, and diagnostic messages are displayed through the graphical local control panel. Field wiring passes through the standard cable entries, and the gland positions remain in their original arrangement because no entry adaptation is installed. The printed circuit boards are not coated, so the drive should be protected from corrosive gases, conductive dust, excessive humidity, and other airborne contaminants that could affect exposed electronics. Its enclosure offers external protection, but installation conditions must still account for the uncoated internal boards. The integrated filter, local display, and cable-entry arrangement support direct installation in HVAC control panels without additional interface hardware.

A Option
No A Option
Adaptation A
Standard Cable Entries
Adaptation B
No adaptation
B Option
No B Option
Brake - Safe Stop
No brake chopper
C0 Option MCO
No C0 option
C1 Option
No C1 option
Coating PCB
Not coated PCB
D Option
No D option
Horse Power
40 HP
LCP
Graphical Loc. Cont. Panel
Mains Option
No Mains Option
Mains Voltage
380 - 480 VAC
Power Phase
Three Phase Power
Power Rating
30 KW
Product Group
VLT HVAC Drive
Protection Level
IP55 / Type 12
RFI Filter
RFI Class A1/B (C1)
Series Identifier
102
Software Language Pack
Standard Language Pack

Frequently Asked Questions about 131B4268:

Q: What type of power phase does the Danfoss 131B4268 require?

A: The 131B4268 drive operates on a three-phase power supply.

Q: What is the horsepower rating of the 131B4268 drive?

A: This VLT FC 102 drive is rated for applications up to 40 horsepower.

Q: What protection level does the Danfoss 131B4268 offer?

A: The protection level for this model is IP55 / Type 12, providing resistance to dust and water ingress.

Q: What input voltage range is supported by the 131B4268 HVAC drive?

A: The 131B4268 supports a mains voltage input range from 380 to 480 VAC.

Q: What type of RFI filter is provided with the Danfoss 131B4268?

A: RFI filtering for the 131B4268 is rated at Class A1/B (C1).


Internal Product Review